Yaskawa oPr fault code meaning
Yaskawa / oPr
Series: CH700, ES700, GA700
Improper operator connection
drive
Meaning:
Possible causes
Source: CH700 Technical Manual P351; ES700 Technical Manual P317; GA700 Technical Manual P375
Series: D1000
Faulty operator connection
drive
Meaning: The connection between the regenerative converter and the operator is open (when operation by commands from the operator is selected). (Note) The "oPr fault" occurs when all the following conditions are met: • o2-06=1 is set (the regenerative converter output is cut off when an open operator connection is detected). • The operator issues a run command (when b1-02=0 or LOCAL operation is selected).
Possible causes
- Incorrect wiring between the operator panel and the regenerative converter
Source: D1000 Series Instruction Manual P97
Series: D1000R
Faulty operator connection
drive
Meaning: The connection between the regenerative converter and the operator is open (when "Run using commands from the operator" is selected). (Note) The "oPr fault" occurs when all of the following conditions are met: o2-06=1 is set (the regenerative converter output is cut off when an open operator connection is detected). The operator issues a run command (b1-02=0 or when LOCAL operation is selected).
Possible causes
- Incorrect wiring between the operator panel and the regenerative converter
Source: D1000R Series Instruction Manual P73
Series: R1000
Faulty operator connection
drive
Meaning: The connection between the regenerative unit and the operator is open (when operation by commands from the operator is selected). (Note) The "oPr fault" occurs when all of the following conditions are met: o2-06=1 is set (disable regenerative unit output when an open connection to the operator is detected); the operator issues a run command (when b1-02=0 or LOCAL operation is selected).
Possible causes
- Incorrect wiring between the operator and the regenerative unit.
Source: R1000 Series Instruction Manual P79