Siemens F7410 fault code meaning
Siemens / F7410
Series: V90
Current controller output limited
servo drive
Meaning: The condition "I_act = 0 and Uq_set_1 is limited for longer than 16 ms" exists. Possible causes: The motor is not connected or the motor contactor is open. No DC bus voltage. The motor module is damaged. Connect the motor or check the motor contactor.
Possible causes
Source: SINAMICS V90 PROFINET, SIMOTICS S-1FL6 Operating Instructions P371