Siemens F60047 fault code meaning
Siemens / F60047
Series: DCM-6RA80
Analog input 1 open
DC drive
Meaning: Analog input 1 (X177.27/28) of CUD is open. The unit reports this fault when p50700 = 2 (i.e., the unipolar current input (+4 mA ... +20 mA) is supervised) and the input current is less than 2 mA. Possible fault causes: - Open cable or poor contact. - Incorrect setting of parameter p50710.
Possible causes
Source: SINAMICS DCM, Parameter Manual, firmware version 1.5 SP2 (based on 5.1 SP2) P1220