Siemens F60046 fault code meaning
Siemens / F60046
Series: DCM-6RA80
Analog input "Main setting" open
DC drive
Meaning: The analog input "Main setting" (X177.25/26) of CUD is open. The unit reports this fault when p50700 = 2 (i.e., the unipolar current input (+4 mA ... +20 mA) is supervised) and the input current is less than 2 mA. Possible fault causes: - Open cable or poor contact. - Incorrect setting of parameter p50700.
Possible causes
Source: SINAMICS DCM, Parameter Manual, firmware version 1.5 SP2 (based on 5.1 SP2) P1220