Siemens F35836 fault code meaning

Siemens / F35836

Series: DCM-6RA80

TM DRIVE-CLiQ: DRIVE-CLiQ data transmission error

DC drive

Meaning: %2 Message class: Internal communication (DRIVE-CLiQ) fault (12) Drive object: DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S, TM150, TM15DI_DO, TM31 Component: Terminal module (TM) Propagation: BICO Response: OFF1 (OFF2) Acknowledgment: Immediate Cause: DRIVE-CLiQ communication between the control unit and the associated terminal module is faulty. Data cannot be sent. Fault cause: 65 (= 41 hexadecimal): Telegram type mismatch with the send list. Note on the message value: Detailed information is encoded in the message value (r0949/r2124) as follows: 0000yyxx hexadecimal: yy = component number, xx = fault cause

Possible causes

Source: SINAMICS DCM, Parameter Manual, firmware version 1.5 SP2 (based on 5.1 SP2) P1179

Series: G130-G150

TM DRIVE-CLiQ: DRIVE-CLiQ data transmission error

converter

Meaning: %2 Message class: Internal communication (DRIVE-CLiQ) fault (12) Drive object: B_INF, TM120, TM150, TM31, TM54F_MA, TM54F_SL, VECTOR_G Component: Terminal module (TM) Broadcast: BICO Reaction: OFF1 (OFF2) Acknowledgment: Immediate Cause: Fault in DRIVE-CLiQ communication between the control unit and the associated terminal module. Data cannot be sent. Fault cause: 65 (= 41 hexadecimal): Telegram type mismatch with the send list. Note on the message value: Detailed information is encoded in the message value (r0949/r2124) as follows: 0000yyxx hexadecimal: yy = component number, xx = fault cause

Possible causes

Source: SINAMICS G130_G150 P1977

Series: S120-S150

TM DRIVE-CLiQ: DRIVE-CLiQ data transmission error

converter

Meaning:

Possible causes

Source: SINAMICS S120_S150 P3174

Series: S220

TM DRIVE-CLiQ: DRIVE-CLiQ data transmission error

converter

Meaning:

Possible causes

Source: SINAMICS S220 Converter P2710