Siemens F34886 fault code meaning
Siemens / F34886
Series: DCM-6RA80
VSM DRIVE-CLiQ (CU): Error sending DRIVE-CLiQ data
DC drive
Meaning: %2 Message class: Internal communication (DRIVE-CLiQ) fault (12) Drive object: DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S, TM150, TM15DI_DO, TM31 Component: Voltage supervision module (VSM) Propagation: LOCAL Response: None (OFF1, OFF2) Acknowledgment: Immediate Cause: DRIVE-CLiQ communication between the control unit and the associated voltage measurement module (VSM) is faulty. Data cannot be sent. Fault cause: 65 (= 41 hexadecimal): Telegram type mismatch with the send list. Note on the message value: Detailed information is encoded in the message value (r0949/r2124) as follows: 0000yyxx hexadecimal: yy = component number, xx = fault cause
Possible causes
Source: SINAMICS DCM, Parameter Manual, firmware version 1.5 SP2 (based on 5.1 SP2) P1160
Series: G120-CU250S-2
VSM DRIVE-CLiQ (CU): Error sending DRIVE-CLiQ data
converter
Meaning: DRIVE-CLiQ communication between the control unit and the associated voltage measurement module (VSM) is faulty. Data cannot be sent. Fault cause: 65 (= 41 hexadecimal): Telegram type mismatch with the send list. Note on the information value: Detailed information is encoded in the information value (r0949/r2124) as follows: 0000yyxx hexadecimal: yy = component number, xx = fault cause
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1091
Series: G130-G150
CU DRIVE-CLiQ: Error when sending DRIVE-CLiQ data
converter
Meaning:
Possible causes
Source: G150 P989