Siemens F30801 fault code meaning

Siemens / F30801

Series: DCM-6RA80

Power unit DRIVE-CLiQ: Sign-of-life fault

DC drive

Meaning: %2 Message class: Internal communication (DRIVE-CLiQ) fault (12) Drive object: DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S Component: Control unit (CU) Propagation: LOCAL Reaction: OFF2 Acknowledgment: Immediately Cause: A fault has occurred in DRIVE-CLiQ communication between the control unit and the associated power unit. The processing load may be too large. Fault cause: 10 (= 0A hexadecimal): The sign-of-life bit is not set in the received telegram. Note on the message value: Detailed information is encoded in the message value (r0949/r2124) as follows: 0000yyxx hexadecimal: yy = Component number, xx = Fault cause

Possible causes

Source: SINAMICS DCM, Parameter Manual, Firmware Version 1.5 SP2 (based on 5.1 SP2) P1051

Series: G120-CU250S-2

Power unit DRIVE-CLiQ: Sign-of-life fault

converter

Meaning:

Possible causes

Source: SINAMICS G120, Control Unit CU250S-2 P1487

Series: G130-G150

Power unit DRIVE-CLiQ: Sign-of-life missing

converter

Meaning:

Possible causes

Source: G150 P922

Series: G200

Power unit DRIVE-CLiQ: Heartbeat signal fault

converter

Meaning: %2 Component: Control unit (CU) Reaction: OFF2 Acknowledgment: Immediate Cause: An error occurred in DRIVE-CLiQ communication between the converter and the associated power unit. The computation time load may be too large.

Possible causes

Source: SINAMICS G200 converter P774

Series: S200

Power unit: Sign of life missing

servo drive

Meaning: %2 Component: Control unit (CU) Response: OFF2 Acknowledgment: Immediate Cause: Internal communication error. The computation load may be too large. Message value (r0949/r2124): 0000yyxx hexadecimal: yy = component number, xx = fault cause xx = 0A hexadecimal (10 decimal): The sign-of-life bit is not set in the received telegram.

Possible causes

Source: SINAMICS S200 Compact_SIMOTICS S-1FL2 and S-1FL1 P541

Series: S220

Power unit DRIVE-CLiQ: Heartbeat signal fault

converter

Meaning: %2 Model: Servo, Vector Component: Control unit (CU) Broadcast: Local Response: OFF2 Acknowledgment: Immediate Cause: DRIVE-CLiQ communication error between the control unit and the associated power unit. The computation time load may be too large. Message value (r0949/r2124): 0000yyxx hexadecimal: yy = component number, xx = fault cause xx = 0A hexadecimal (10 decimal): The heartbeat signal bit in the received telegram is not set.

Possible causes

Source: SINAMICS S220 Converter P2493