Siemens F30801 fault code meaning
Siemens / F30801
Series: DCM-6RA80
Power unit DRIVE-CLiQ: Sign-of-life fault
DC drive
Meaning: %2 Message class: Internal communication (DRIVE-CLiQ) fault (12) Drive object: DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S Component: Control unit (CU) Propagation: LOCAL Reaction: OFF2 Acknowledgment: Immediately Cause: A fault has occurred in DRIVE-CLiQ communication between the control unit and the associated power unit. The processing load may be too large. Fault cause: 10 (= 0A hexadecimal): The sign-of-life bit is not set in the received telegram. Note on the message value: Detailed information is encoded in the message value (r0949/r2124) as follows: 0000yyxx hexadecimal: yy = Component number, xx = Fault cause
Possible causes
Source: SINAMICS DCM, Parameter Manual, Firmware Version 1.5 SP2 (based on 5.1 SP2) P1051
Series: G120-CU250S-2
Power unit DRIVE-CLiQ: Sign-of-life fault
converter
Meaning:
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1487
Series: G130-G150
Power unit DRIVE-CLiQ: Sign-of-life missing
converter
Meaning:
Possible causes
Source: G150 P922
Series: G200
Power unit DRIVE-CLiQ: Heartbeat signal fault
converter
Meaning: %2 Component: Control unit (CU) Reaction: OFF2 Acknowledgment: Immediate Cause: An error occurred in DRIVE-CLiQ communication between the converter and the associated power unit. The computation time load may be too large.
Possible causes
Source: SINAMICS G200 converter P774
Series: S200
Power unit: Sign of life missing
servo drive
Meaning: %2 Component: Control unit (CU) Response: OFF2 Acknowledgment: Immediate Cause: Internal communication error. The computation load may be too large. Message value (r0949/r2124): 0000yyxx hexadecimal: yy = component number, xx = fault cause xx = 0A hexadecimal (10 decimal): The sign-of-life bit is not set in the received telegram.
Possible causes
Source: SINAMICS S200 Compact_SIMOTICS S-1FL2 and S-1FL1 P541
Series: S220
Power unit DRIVE-CLiQ: Heartbeat signal fault
converter
Meaning: %2 Model: Servo, Vector Component: Control unit (CU) Broadcast: Local Response: OFF2 Acknowledgment: Immediate Cause: DRIVE-CLiQ communication error between the control unit and the associated power unit. The computation time load may be too large. Message value (r0949/r2124): 0000yyxx hexadecimal: yy = component number, xx = fault cause xx = 0A hexadecimal (10 decimal): The heartbeat signal bit in the received telegram is not set.
Possible causes
Source: SINAMICS S220 Converter P2493