Siemens F30701 fault code meaning
Siemens / F30701
Series: G120-CU240B-E-2
SI motion P2: STOP B triggered
converter
Meaning: STOP B stops the drive (by braking along the OFF3 deceleration ramp). Once the speed falls below the threshold set in p9360, message C30700 "STOP A triggered" is output as a result of this fault. Possible causes: - Processor 1 issued a stop request. - Subsequent response to message C30714 "SI motion P2: Safely-Limited Speed exceeded". - Subsequent response to message C30711 "SI motion P2: monitoring channel error". - Subsequent response to message C30707 "SI motion P2: tolerance of Safe Operating Stop exceeded".
Possible causes
Source: SINAMICS G120 Control Unit CU240B- 2_CU240E- 2 P891
Series: G120-CU250S-2, G120D
SI motion P2: STOP B triggered
converter
Meaning:
Possible causes
Source: SINAMICS G120 Control Units CU250S-2 P1133; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P932
Series: S210
SI motion P2: SS1 triggered
servo drive
Meaning: SS1 stops the drive. After the time set in p9556 or the speed threshold set in p9560 is exceeded, message F30700 "SI Motion P2: STO triggered" is output as a result of this fault. Possible causes: - Another monitoring channel has issued a stop request. - Subsequent response to the following messages: A30714, A30711, A30707, A30716
Possible causes
Source: SINAMICS S210_SIMOTICS S-1FK2 and S-1FT2 P922