Siemens F30061 fault code meaning

Siemens / F30061

Series: G120-CU250S-2

Bypass contactor status monitoring

converter

Meaning: %1 bin Drive object: CU250S_S, CU250S_S_CAN, CU250S_S_DP, CU250S_S_PN Reaction: OFF2 (OFF1, None) Acknowledgment: Immediately (power-on) Cause: A feedback signal has been interconnected for the bypass contactor, and monitoring has been enabled. After the contactor was closed/opened, the correct feedback was not received within the monitoring time set in p0255[1].

Possible causes

Source: SINAMICS G120, Control Unit CU250S-2 P1469

Series: G130-G150

Bypass contactor status monitoring

converter

Meaning: %1 bin Message class: Line module fault (13) Drive object: B_INF, VECTOR_G Component: Power section Broadcast: LOCAL Reaction: OFF2 (OFF1, none) Acknowledgment: Immediate (power-on) Cause: A feedback signal has been interconnected for the bypass contactor, and monitoring has been enabled. After the contactor was closed/opened, the correct feedback was not received within the monitoring time set in p0255[1, 3].

Possible causes

Source: SINAMICS G130_G150 P1734

Series: S110

Bypass contactor status monitoring

servo drive

Meaning: %1 bin. Drive object: SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN. Reaction: OFF2 (OFF1, none). Acknowledgment: Immediate (power-on). Cause: After the monitoring time (p0255[1]) expired, the actual status monitored for the bypass contactor differed from the set status.

Possible causes

Source: SINAMICS S110 P1085

Series: S120-S150

Bypass contactor status monitoring

converter

Meaning: %1 bin Message class: Power supply module fault (13) Drive object: A_INF, B_INF, R_INF, S_INF, SERVO, SERVO_AC, SERVO_I_AC, VECTOR, VECTOR_AC, VECTOR_I_AC Component: Power section Broadcast: LOCAL Reaction: OFF2 (OFF1, None) Acknowledgment: Immediate (Power-on) Cause: A feedback signal has been interconnected for the bypass contactor, and monitoring has been activated. After the contactor was closed/opened, the correct feedback was not received within the monitoring time set in p0255[1, 3].

Possible causes

Source: SINAMICS S120_S150 P2903