Siemens F30060 fault code meaning
Siemens / F30060
Series: G120-CU250S-2
Precharging contactor status monitoring
converter
Meaning: %1 bin Drive object: CU250S_S, CU250S_S_CAN, CU250S_S_DP, CU250S_S_PN Reaction: OFF2 (OFF1, None) Acknowledgment: Immediately (power-on) Cause: A feedback signal has been interconnected for the precharging contactor (ALM, SLM, BLM diode) or the power supply contactor (BLM thyristor), and monitoring has been enabled. After the contactor was closed/opened, the correct feedback was not received within the monitoring time set in p0255[0].
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1469
Series: G130-G150
Precharging contactor status monitoring
converter
Meaning: %1 bin Message class: Line module fault (13) Drive object: B_INF, VECTOR_G Component: Power section Broadcast: LOCAL Reaction: OFF2 (OFF1, none) Acknowledgment: Immediate (power-on) Cause: A feedback signal has been interconnected for the precharging contactor (ALM, SLM, BLM diode) or power supply contactor (BLM thyristor), and monitoring has been enabled. After the contactor was closed/opened, the correct feedback was not received within the monitoring time set in p0255[0, 2].
Possible causes
Source: SINAMICS G130_G150 P1734
Series: S110
Precharging contactor status monitoring
servo drive
Meaning: %1 bin. Drive object: SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN. Reaction: OFF2 (OFF1, none). Acknowledgment: Immediate (power-on). Cause: After the monitoring time (p0255[0]) expired, the actual status of the precharging contactor differed from the set status. Bit 0: Monitoring time exceeded. Bit 1: The contactor opened during operation. Bit 2: The contactor closed while in the "Off" state.
Possible causes
Source: SINAMICS S110 P1085
Series: S120-S150
Precharging contactor status monitoring
converter
Meaning: %1 bin Message class: Power supply module fault (13) Drive object: A_INF, B_INF, R_INF, S_INF, SERVO, SERVO_AC, SERVO_I_AC, VECTOR, VECTOR_AC, VECTOR_I_AC Component: Power section Broadcast: LOCAL Reaction: OFF2 (OFF1, None) Acknowledgment: Immediate (Power-on) Cause: A feedback signal has been interconnected for the precharging contactor (ALM, SLM, BLM diode) or the power supply contactor (BLM thyristor), and monitoring has been activated. After the contactor was closed/opened, the correct feedback was not received within the monitoring time set in p0255[0, 2].
Possible causes
Source: SINAMICS S120_S150 P2902