Siemens F30058 fault code meaning

Siemens / F30058

Series: G130-G150, S120-S150

Power unit: Heatsink fan damaged

converter

Meaning: The heatsink fan feedback reports a fault. - The fan is damaged. - The fan has a locked rotor. - The feedback is incorrect. - The fan power supply is interrupted (only when r0193.13 = 1).

Possible causes

Source: SINAMICS G130_G150 P1733; SINAMICS S120_S150 P2902

Series: G200, G220

Power unit: Main fan damaged

converter

Meaning: %1 bin Component: Power unit Reaction: OFF2 (OFF1, None) Acknowledgment: Immediate Cause: The main fan reported a fault or a communication error occurred with the fan. - The fan is damaged. - The fan has a locked rotor. - The feedback information is incorrect.

Possible causes

Source: SINAMICS G200 converter P762; SINAMICS G220 converter P1460

Series: G210

Power unit: Main fan damaged

converter

Meaning: %1 bin Component: Power unit Faults and alarms 5.2 List of faults and alarms SINAMICS G210 Converter 1200 Parameter Manual, 07/2026, FW V6.7, A5E54375461F AA

Possible causes

Source: SINAMICS G210 converter P1202

Series: G210X

Power unit: Main fan damaged

converter

Meaning: %1 bin Component: Power unit. Faults and alarms 5.2 List of faults and alarms SINAMICS G210X Converter 1026 Parameter Manual, 07/2026, FW V6.7, A5E54375466F AA

Possible causes

Source: SINAMICS G210X Converter P1028

Series: S200

Power unit: Heatsink fan damaged

servo drive

Meaning: %1 bin Component: Power unit. Reaction: OFF2 Acknowledgment: Immediate. Cause: The heatsink fan reported a fault, or a communication error occurred with the fan. - The fan is damaged. - The fan has a locked rotor. - The feedback information is incorrect.

Possible causes

Source: SINAMICS S200 Compact_SIMOTICS S-1FL2 and S-1FL1 P532

Series: S220

Power unit: Main fan damaged

converter

Meaning: %1 bin Model: Servo, Vector Component: Power unit Broadcast: Global Response: OFF2 (OFF1, None) Acknowledgment: Immediate Cause: The main fan has reported a fault, or a communication error with the fan has occurred. - Fan damaged. - Fan locked rotor. - Incorrect feedback information.

Possible causes

Source: SINAMICS S220 Converter P2474