Siemens F30024 fault code meaning
Siemens / F30024
Series: G110M, G120-CU240B-E-2, G120-CU250S-2
Power unit: Thermal model overheat
converter
Meaning: The temperature difference between the heatsink and the chip has exceeded the permissible critical value. - The permissible duty cycle was not maintained. - Insufficient ventilation or fan fault. - Overload. - Ambient temperature too high. - Pulse frequency too high. See: r0037 (Power unit temperature)
Possible causes
Source: SINAMICS G110M P739; SINAMICS G120, Control Unit CU240B-2_CU240E-2 P764; SINAMICS G120, Control Unit CU250S-2 P1459
Series: G115D, G120C
"Overtemperature thermal model"
converter
Meaning:
Possible causes
Source: SINAMICS G115D P687; SINAMICS G120C P615
Series: G120D
Power unit: Thermal model overheat
converter
Meaning: The temperature difference between the heatsink and the chip exceeds the permissible critical value. - The permissible duty cycle has not been maintained. - Insufficient ventilation or fan fault. - Overload. - Ambient temperature too high. - Pulse frequency too high. See also: r0037 (Power unit temperature)
Possible causes
Source: SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P917
Series: G120X
Thermal model overheat
converter
Meaning:
Possible causes
Source: SINAMICS G120X converter P1438
Series: G120XA
Power unit: Thermal model overheat
converter
Meaning: The temperature difference between the heatsink and the chip has exceeded the permissible threshold. - Permissible duty cycle not maintained. - Insufficient ventilation or fan fault. - Overload. - Ambient temperature too high. - Pulse frequency too high. See also: r0037
Possible causes
Source: SINAMICS G120XA PN converter P1317
Series: G130-G150, S120-S150
Power unit: Thermal model overheat
converter
Meaning: The temperature difference between the heatsink and the chip has exceeded the permissible threshold. - The permissible duty cycle was not maintained. - Insufficient ventilation or fan fault. - Overload. - Ambient temperature too high. - Pulse frequency too high. See also: r0037
Possible causes
Source: SINAMICS G130_G150 P1720; SINAMICS S120_S150 P2887
Series: G210, G210X, G220, S220
"thermal model"
converter
Meaning:
Possible causes
Source: SINAMICS G210 converter P934; SINAMICS G210X converter P801; SINAMICS G220 converter P1121; SINAMICS S220 converter P1942
Series: S110
thermal model
servo drive
Meaning:
Possible causes
Source: SINAMICS S110 P886
Series: S210
Power unit: Thermal model overheat
servo drive
Meaning: The temperature difference between the heatsink and the chip has exceeded the permissible critical value. - The permissible duty cycle has not been maintained. - Insufficient ventilation, fan fault. - Overload. - Ambient temperature too high. - Pulse frequency too high. See also: r0037 (Drive temperature).
Possible causes
Source: SINAMICS S210_SIMOTICS S-1FK2 P515