Siemens F30024 fault code meaning

Siemens / F30024

Series: G110M, G120-CU240B-E-2, G120-CU250S-2

Power unit: Thermal model overheat

converter

Meaning: The temperature difference between the heatsink and the chip has exceeded the permissible critical value. - The permissible duty cycle was not maintained. - Insufficient ventilation or fan fault. - Overload. - Ambient temperature too high. - Pulse frequency too high. See: r0037 (Power unit temperature)

Possible causes

Source: SINAMICS G110M P739; SINAMICS G120, Control Unit CU240B-2_CU240E-2 P764; SINAMICS G120, Control Unit CU250S-2 P1459

Series: G115D, G120C

"Overtemperature thermal model"

converter

Meaning:

Possible causes

Source: SINAMICS G115D P687; SINAMICS G120C P615

Series: G120D

Power unit: Thermal model overheat

converter

Meaning: The temperature difference between the heatsink and the chip exceeds the permissible critical value. - The permissible duty cycle has not been maintained. - Insufficient ventilation or fan fault. - Overload. - Ambient temperature too high. - Pulse frequency too high. See also: r0037 (Power unit temperature)

Possible causes

Source: SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P917

Series: G120X

Thermal model overheat

converter

Meaning:

Possible causes

Source: SINAMICS G120X converter P1438

Series: G120XA

Power unit: Thermal model overheat

converter

Meaning: The temperature difference between the heatsink and the chip has exceeded the permissible threshold. - Permissible duty cycle not maintained. - Insufficient ventilation or fan fault. - Overload. - Ambient temperature too high. - Pulse frequency too high. See also: r0037

Possible causes

Source: SINAMICS G120XA PN converter P1317

Series: G130-G150, S120-S150

Power unit: Thermal model overheat

converter

Meaning: The temperature difference between the heatsink and the chip has exceeded the permissible threshold. - The permissible duty cycle was not maintained. - Insufficient ventilation or fan fault. - Overload. - Ambient temperature too high. - Pulse frequency too high. See also: r0037

Possible causes

Source: SINAMICS G130_G150 P1720; SINAMICS S120_S150 P2887

Series: G210, G210X, G220, S220

"thermal model"

converter

Meaning:

Possible causes

Source: SINAMICS G210 converter P934; SINAMICS G210X converter P801; SINAMICS G220 converter P1121; SINAMICS S220 converter P1942

Series: S110

thermal model

servo drive

Meaning:

Possible causes

Source: SINAMICS S110 P886

Series: S210

Power unit: Thermal model overheat

servo drive

Meaning: The temperature difference between the heatsink and the chip has exceeded the permissible critical value. - The permissible duty cycle has not been maintained. - Insufficient ventilation, fan fault. - Overload. - Ambient temperature too high. - Pulse frequency too high. See also: r0037 (Drive temperature).

Possible causes

Source: SINAMICS S210_SIMOTICS S-1FK2 P515