Siemens F30022 fault code meaning

Siemens / F30022

Series: G110M, G120-CU230P-2

Power module: monitoring UCE

converter

Meaning:

Possible causes

Source: SINAMICS G110M Converter P382; Converter SINAMICS G120, with Control Unit CU230P-2 P497

Series: G115D

Power unit: U_ce monitoring

converter

Meaning:

Possible causes

Source: SINAMICS G115D P793

Series: G120-CU240B-E-2, G120-CU250S-2

Power unit: U_ce monitoring

converter

Meaning: Semiconductor collector-emitter voltage monitoring (U_ce) was triggered in the power unit. Possible causes: - The fiber-optic cable is disconnected. - The power supply to the IGBT control component is missing. - A short circuit is present at the power unit output. - A power unit semiconductor is damaged.

Possible causes

Source: SINAMICS G120, Control Unit CU240B-2_CU240E-2 P764; SINAMICS G120, Control Unit CU250S-2 P1019

Series: G120C

Power module: Monitoring VCE

converter

Meaning:

Possible causes

Source: Converter SINAMICS G120C P409

Series: G120D

Power unit: U_ce monitoring

converter

Meaning: Semiconductor collector-emitter voltage monitoring (U_ce) has responded in the power unit. Possible causes: - The fiber-optic cable is open. - The power supply to the IGBT control assembly is missing. - There is a short circuit at the power unit output. - A power unit semiconductor is damaged.

Possible causes

Source: SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P917

Series: G120P-Cabinet

Power module: Monitoring U_ce

converter

Meaning:

Possible causes

Source: SINAMICS G120P Cabinet P509

Series: G120XA

Power unit: U_ce monitoring

converter

Meaning: In the power unit, semiconductor collector-emitter voltage monitoring (U_ce) has responded. Possible causes: - Fiber-optic cable open. - No power supply to the IGBT control component. - Short circuit at the power unit output. - Power unit semiconductor damaged.

Possible causes

Source: SINAMICS G120XA PN converter P1317

Series: G130-G150

Power unit: U_ce monitoring

converter

Meaning: %1 bin Message class: Ground fault/phase-to-phase short circuit (7) Drive object: B_INF, VECTOR_G Component: Power section Broadcast: LOCAL Reaction: OFF2 Acknowledgment: Power-on Cause: Semiconductor collector-emitter voltage monitoring (U_ce) has responded in the power unit. Possible causes: - The fiber-optic cable is disconnected. - The power supply for the IGBT control component is missing. - A short circuit is present at the power unit output. - A power unit semiconductor is damaged.

Possible causes

Source: SINAMICS G130_G150 P1720

Series: S120-S150

Power unit: U_ce monitoring

converter

Meaning: %1 bin Message class: Ground fault/phase-to-phase short circuit (7) Drive object: A_INF, B_INF, R_INF, S_INF, SERVO, SERVO_AC, SERVO_I_AC, VECTOR, VECTOR_AC, VECTOR_I_AC Component: Power section Broadcast: LOCAL Reaction: OFF2 Acknowledgment: Power-on Cause: Semiconductor collector-emitter voltage monitoring (U_ce) has responded in the power unit. Possible causes: - The fiber-optic cable is disconnected. - The power supply for the IGBT control component is missing. - Short circuit at the power unit output. - The power unit semiconductor is damaged.

Possible causes

Source: SINAMICS S120_S150 P2887