Siemens F30017 fault code meaning

Siemens / F30017

Series: G110M, G115D, G120-CU240B-E-2, G120D

Power unit: Hardware current limit responds too frequently

converter

Meaning: Hardware current limiting responds too frequently in the individual phases (see A30031, A30032, A30033). The permissible number of limit exceedances depends on the category and type of power unit. - Incorrect closed-loop control parameter settings. - Fault in the motor or power cable. - Power cable exceeds the maximum permissible length. - Motor load too large. - Power unit damaged.

Possible causes

Source: SINAMICS G110M P737; SINAMICS G115D P793; SINAMICS G120 control unit CU240B_E-2 P686; SINAMICS G120D control unit CU240D- 2_CU250D- 2 P916

Series: G120-CU250S-2

Power unit: Hardware current limit responds too frequently

converter

Meaning: %1 bin Drive object: CU250S_S, CU250S_S_CAN, CU250S_S_DP, CU250S_S_PN Reaction: OFF2 Acknowledgment: Immediately Cause: Hardware current limiting responds too frequently in the individual phases (see A30031, A30032, A30033). The permissible number of limit exceedances depends on the power unit model and type. For the infeed: - Incorrect closed-loop control parameter settings. - Infeed load too large. - Incorrect voltage monitoring module connection. - Rectifier reactor missing or of the incorrect type. - Power unit damaged. For the Motor Module: - Incorrect closed-loop control parameter settings. - Fault in the motor or power cable. - The power cable exceeds the maximum permissible length. - Motor load too large. - Power unit damaged.

Possible causes

Source: SINAMICS G120, Control Unit CU250S-2 P1456

Series: G120C, G120X, G120XA

Power unit: Hardware current limit responds too frequently

converter

Meaning:

Possible causes

Source: SINAMICS G120C P706; SINAMICS G120X Converter P1405; SINAMICS G120XA PN Converter Compact Operating Instructions P8

Series: G130-G150

Power unit: Hardware current limit responds too frequently

converter

Meaning: %1 bin Message class: Power component fault (5) Drive object: B_INF, VECTOR_G Component: Power section Broadcast: LOCAL Reaction: OFF2 Acknowledgment: Immediate

Possible causes

Source: SINAMICS G130_G150 P1717

Series: G200

Power unit: Hardware current limit responding too frequently

converter

Meaning: %1 bin Component: Power unit Reaction: OFF2 Acknowledgment: Immediate System messages 14.3 Faults and alarms SINAMICS G200 Basic converter 622 Operating Instructions, 12/2025, FW V6.6, A5E54053398B AA

Possible causes

Source: SINAMICS G200 Basic converter P624

Series: S200

Power unit: Hardware current limit responding too frequently

servo drive

Meaning: %1 bin System messages 12.3 Faults and alarms. SINAMICS S200 Compact servo drive system with SIMOTICS S-1FL2 or S-1FL1. 522 Operating Instructions, 10/2025, FW V6.5 HF1, A5E54029715B AB

Possible causes

Source: SINAMICS S200 Compact_SIMOTICS S-1FL2 and S-1FL1 P524

Series: S210

Power unit: Hardware current limit responds too frequently

servo drive

Meaning: %1 bin Component: Power unit. Broadcast: Local. Reaction: OFF2. Acknowledgment: Immediate. Faults and alarms. 18.2 List of faults and alarms. SINAMICS S210 servo drive system with SIMOTICS S-1FK2 and S-1FT2. Operating Instructions, 05/2025, FW V6.4, A5E52380168F AF 1349

Possible causes

Source: SINAMICS S210_SIMOTICS S-1FK2 and S-1FT2 P1351