Siemens F30006 fault code meaning
Siemens / F30006
Series: DCM-6RA80
Power unit: SCR control board
DC drive
Meaning:
Possible causes
Source: SINAMICS DCM, Parameter Manual, Firmware Version 1.5 SP2 (based on 5.1 SP2) P1035
Series: G120-CU250S-2
Power unit: SCR control board
converter
Meaning: The SCR control board (TCB) of the Basic Line Module reports a fault. - No input voltage. - The power supply contactor is not closed. - Input voltage too low. - Input frequency outside the permissible range (45 Hz ...66 Hz). - Short circuit in the DC bus. - Ground fault in the DC bus (during the precharging phase). - The SCR control board voltage is outside the rated range (5 V... 18 V) and the input voltage is > 30 V. - An internal fault occurred in the SCR control board.
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1453
Series: G130-G150
Power unit: SCR control board
converter
Meaning: The SCR control board (TCB) of the Basic Line Module reports a fault. - No input voltage. - The power supply contactor is not closed. - The input voltage is too low. - The input frequency is outside the permissible range (45 Hz ...66 Hz). - A short circuit is present in the DC bus. - A ground fault is present in the DC bus (during the precharging phase). - A short circuit or insulation fault is present in the motor (inverter connected to the DC bus). - The SCR control board voltage is outside the rated range (5 V... 18 V), and the input voltage is > 30 V. - An internal fault has occurred in the SCR control board.
Possible causes
Source: SINAMICS G130_G150 P1714
Series: S120-S150
Power unit: SCR control board
converter
Meaning:
Possible causes
Source: SINAMICS S120_S150 P2880