Siemens F07901 fault code meaning
Siemens / F07901
Series: G110M, G115D, G120-CU240B-E-2, G120-CU250S-2, G120D, G120X, G120XA, G130-G150, S120-S150
Drive: Motor speed too high
converter
Meaning: The maximum permissible positive or negative speed has been exceeded. The maximum permissible positive speed is calculated as follows: minimum(p1082, CI: p1085) + p2162. The maximum permissible negative speed is calculated as follows: maximum(-p1082, CI: p1088) - p2162.
Possible causes
Source: SINAMICS G110M P715; SINAMICS G115D P773; SINAMICS G120, Control Unit CU240B-2_CU240E-2 P744; SINAMICS G120, Control Unit CU250S-2 P1414; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P895; SINAMICS G120X Converter P1388; SINAMICS G120XA PN Converter P1299; SINAMICS G130_G150 P1666; SINAMICS S120_S150 P2817
Series: G120-CU230P-2, G120P-Cabinet
Motor overspeed
converter
Meaning:
Possible causes
Source: Converter SINAMICS G120, equipped with control unit CU230P-2 P494; SINAMICS G120P Cabinet P512
Series: G120C
Drive: Motor speed too high
converter
Meaning: The maximum permissible positive or negative speed was exceeded. The maximum permissible positive speed is calculated as follows: Minimum (p1082). The maximum permissible negative speed is calculated as follows: Maximum (-p1082).
Possible causes
Source: SINAMICS G120C P687
Series: G210X
Drive: Motor speed too high
converter
Meaning: The maximum permissible positive or negative speed has been exceeded. The maximum permissible positive speed is calculated as: minimum (p1082, c1085) + p2162. The maximum permissible negative speed is calculated as: maximum (-p1082, c1088) - p2162.
Possible causes
Source: SINAMICS G210X converter P984
Series: S200
Drive: Motor speed too high
servo drive
Meaning: The maximum permissible positive or negative speed has been exceeded. The maximum permissible positive speed is calculated as: minimum (p1082, p1083, p29072) + p2162. The maximum permissible negative speed is calculated as: maximum (-p1082, p1086, p29073) - p2162.
Possible causes
Source: SINAMICS S200 PROFINET_SIMOTICS S-1FL2 P542
Series: S210
Drive: Motor speed too high
servo drive
Meaning: The maximum permissible positive or negative speed (p1082) has been exceeded.
Possible causes