Siemens F07900 fault code meaning

Siemens / F07900

Series: G110M, G120-CU240B-E-2, G120-CU250S-2

Drive: Motor stalled

converter

Meaning: The motor has operated at the torque limit for longer than the time set in p2177, at a speed below the threshold set in p2175. This message is also triggered if the speed oscillates and the speed loop output repeatedly returns briefly to the limit. The power unit thermal monitoring function may also have reduced the current limit (see p0290), causing the motor to stop. See: p2175 (Motor locked rotor speed threshold), p2177 (Motor locked rotor delay).

Possible causes

Source: SINAMICS G110M P715; SINAMICS G120, Control Unit CU240B-2_CU240E-2 P743; SINAMICS G120, Control Unit CU250S-2 P1413

Series: G115D, G120D

Drive: Motor stalled

converter

Meaning: The motor has operated at the torque limit for longer than the time set in p2177, with the speed below the threshold set in p2175. This message is also triggered if the speed oscillates and the speed loop output repeatedly returns briefly to its limit. The power unit thermal monitoring function may also have reduced the current limit (see p0290), causing the motor to stop. See also: p2175 (Motor locked rotor speed threshold), p2177 (Motor locked rotor delay)

Possible causes

Source: SINAMICS G115D P773; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P895

Series: G120-CU230P-2, G120P-Cabinet

Motor stalled

converter

Meaning:

Possible causes

Source: Converter SINAMICS G120, equipped with control unit CU230P-2 P494; SINAMICS G120P Cabinet P512

Series: G120C

Drive: Motor stalled

converter

Meaning: The motor has been operating at the torque limit for an extended period while below the configured speed threshold. This message is also triggered if the speed oscillates and the speed controller output repeatedly returns briefly to its limit. The power unit thermal monitoring function may also have reduced the current limit (see p0290), causing the motor to stop.

Possible causes

Source: SINAMICS G120C P687

Series: G120X, G120XA

Drive: Motor stalled

converter

Meaning: The motor has operated at the torque limit for longer than the time set in p2177, below the speed threshold set in p2175. This message is also triggered if the speed oscillates and the speed loop output repeatedly returns briefly to the limit. The power unit thermal monitoring function may also have reduced the current limit (see p0290), causing the motor to stop. See also: p2175, p2177

Possible causes

Source: SINAMICS G120X converter P1388; SINAMICS G120XA PN converter P1299

Series: G130-G150

Drive: Motor stalled

converter

Meaning: The motor has operated at the torque limit for longer than the time set in p2177, with its speed below the threshold set in p2175. This message is also triggered if the actual speed oscillates and the speed controller output repeatedly reaches its limit momentarily. If simulation mode is active (p1272 = 1) and closed-loop control with a speed encoder is enabled (p1300 = 21), this locked rotor message is issued when the encoder signal comes from another motor (a motor that does not run according to the torque setpoint of the closed-loop control). See also: p2175 (motor locked rotor speed threshold), p2177 (motor locked rotor delay).

Possible causes

Source: SINAMICS G130_G150 P1666

Series: G210X

Drive: Motor stalled

converter

Meaning: The motor has operated at the torque limit for longer than the time set in p2177, at a speed below the threshold set in p2175. In encoderless vector control (including DDC), this message is also triggered if the load starting current p1610 is set too small, or if the speed fluctuates and the speed controller output frequently reaches the limit. Phase loss has occurred in the motor cable. The power unit thermal monitoring function may also have reduced the current limit (see p0290), causing the motor to stop. See also: p2175 (Locked rotor speed threshold), p2177 (Locked rotor delay time).

Possible causes

Source: SINAMICS G210X converter P984

Series: G220

Drive: Motor stalled

converter

Meaning:

Possible causes

Source: SINAMICS G220 Converter P1371

Series: S110

Drive: Motor stalled/speed loop reached the end stop

servo drive

Meaning: The motor has been operating at the torque limit for longer than the time set in p2177, at a speed below the threshold set in p2175. This message is also triggered if the actual speed oscillates and the speed controller output repeatedly reaches its limit momentarily. See: p2175 (Motor locked rotor speed threshold), p2177 (Motor locked rotor delay time).

Possible causes

Source: SINAMICS S110 P1049

Series: S120-S150

Motor blocked

converter

Meaning:

Possible causes

Source: SINAMICS S120_S150 P2362

Series: S200

Drive: Motor stalled/speed controller reached end stop

servo drive

Meaning: The motor has been running at the torque limit below the speed threshold set in p2175 for more than 0.2 seconds. This message is also triggered if the actual speed oscillates and the speed controller output repeatedly reaches its limit briefly. The message may also be triggered by phase loss in the motor cable. See also: p2175, p2177.

Possible causes

Source: SINAMICS S200 PROFINET_SIMOTICS S-1FL2 P541

Series: S210

Drive: Motor stalled/speed loop reached the end stop

servo drive

Meaning: The motor has been running at the torque limit and below the speed threshold set in p2175 for more than 0.2 seconds. This message is also triggered if the actual speed oscillates and the speed controller output repeatedly reaches its limit momentarily. See also: p2175 (Locked rotor speed threshold).

Possible causes

Source: SINAMICS S210_SIMOTICS S-1FK2 and S-1FT2 P893