Siemens F07895 fault code meaning
Siemens / F07895
Series: G110M
Drive: Pump/fan no-load monitoring
converter
Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected operation without load. The pump is running without lubrication (no pumped liquid), or the fan drive belt is too smooth. The set detection torque threshold may be too low (p2191). See: p2181 (Load monitoring response), p2191 (No-load torque threshold), p2193 (Load monitoring configuration).
Possible causes
Source: SINAMICS G110M P714
Series: G115D, G120-CU240B-E-2
Drive: Pump/fan no-load monitoring
converter
Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected no-load operation. The pump is running without lubrication (no fluid being pumped), or the fan drive belt is too smooth. The configured detection torque threshold (p2191) may be too low. See also: p2181 (load monitoring response), p2191 (no-load torque threshold), p2193 (load monitoring configuration).
Possible causes
Source: SINAMICS G115D P772;SINAMICS G120 Control Unit CU240B- 2_CU240E- 2 P850
Series: G120-CU230P-2
Load monitoring: Pump/fan no load
converter
Meaning:
Possible causes
Source: Converter SINAMICS G120, equipped with control unit CU230P-2 P494
Series: G120-CU250S-2
Drive: Pump/fan no-load monitoring
converter
Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected no-load operation. The pump is running without lubrication (no pumped liquid), or the fan drive belt is too smooth. The detection torque threshold setting may be too low (p2191). See: p2181 (Load monitoring response), p2193 (Load monitoring configuration).
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1043
Series: G120C
Drive: Pump/fan no-load monitoring
converter
Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected no-load operation. The pump is running dry (no pumped liquid), or the fan drive belt is too smooth. The detection torque threshold setting may be too low (p2191). See also: p2191 (No-load torque threshold).
Possible causes
Source: SINAMICS G120C P687
Series: G120D
Drive: Pump/fan no-load monitoring
converter
Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected no-load operation. The pump is running dry (no pumped liquid), or the fan drive belt is too smooth. The detection torque threshold setting may be too low (p2191). See also: p2181 (Load monitoring response), p2193 (Load monitoring configuration).
Possible causes
Source: SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P895
Series: G120X, G210X, G220
Drive: Pump/fan no-load monitoring
converter
Meaning:
Possible causes
Source: SINAMICS G120X Converter P1387; SINAMICS G210X Converter P982; SINAMICS G220 Converter P1370
Series: G120XA
Drive: Pump/fan no-load monitoring
converter
Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected operation without a load. The pump is running dry (no fluid being pumped), or the fan drive belt is too smooth. The detection torque threshold setting may be too low (p2191). See also: p2181, p2191, p2193
Possible causes
Source: SINAMICS G120XA PN converter P1298
Series: G210, S220
Drive: Pump/fan no-load monitoring
converter
Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Pump/fan monitoring has detected no-load operation. The pump is running dry (no medium to convey), or the fan drive belt has broken. The configured detection torque threshold may be too low (p2191). See also: p2181 (Load monitoring response), p2191 (No-load torque threshold), p2193 (Load monitoring configuration).
Possible causes
Source: SINAMICS G210 converter P1154; SINAMICS S220 converter P2351