Siemens F07575 fault code meaning
Siemens / F07575
Series: G120-CU250S-2
Drive: Motor encoder not ready
converter
Meaning:
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1402
Series: G130-G150
Drive: Motor encoder not ready
converter
Meaning:
Possible causes
Source: G150 P878
Series: G200, G210X
Drive: Motor encoder not ready
converter
Meaning: The motor encoder reports that it is not ready. - Initialization of encoder 1 (motor encoder) failed. - The "Park encoder" function is currently active (encoder control word G1_STW.14 = 1). - The encoder module is damaged.
Possible causes
Source: SINAMICS G200 converter P717; SINAMICS G210X converter P978
Series: G210, S220
Drive: Motor encoder not ready
converter
Meaning: The motor encoder reports that it is not ready. - Motor encoder initialization failure. - The "Park encoder" function is currently active (encoder control word G1_STW.14 = 1). - The encoder interface (encoder module) is disabled. - The encoder module is damaged.
Possible causes
Source: SINAMICS G210 converter P1143; SINAMICS S220 converter P2334
Series: S110
Drive: Motor encoder not ready
servo drive
Meaning: The motor encoder reports that it is not ready. - Initialization of encoder 1 (motor encoder) failed. - The "Park encoder" function is currently valid (encoder control word G1_STW.14 = 1). - The encoder interface (encoder module) is disabled (p0145). - The encoder module is damaged.
Possible causes
Source: SINAMICS S110 P1040
Series: S120-S150
Drive: Motor encoder not ready
converter
Meaning: The motor encoder reports that it is not ready. - Initialization of encoder 1 (motor encoder) failed. - The "Park encoder" function is currently valid (encoder control word G1_STW.14 = 1). - The encoder interface (encoder module) is disabled (p0145). - The encoder module is damaged.
Possible causes
Source: SINAMICS S120_S150 P2793
Series: S200
Drive: Motor encoder not ready
servo drive
Meaning: The motor encoder reports that it is not ready. - Initialization of encoder 1 (motor encoder) failed. - The "Park encoder" function is currently enabled (encoder control word G1_STW.14 = 1). - The encoder module is damaged.
Possible causes
Source: SINAMICS S200 Compact_SIMOTICS S-1FL2 and S-1FL1 P511
Series: S210
Drive: Motor encoder not ready
servo drive
Meaning: The motor encoder reports that it is not ready. - Initialization of encoder 1 (motor encoder) failed. - The "Park encoder" function is currently active (encoder control word G1_STW.14 = 1). - The encoder interface (encoder module) is disabled (p0145). - The encoder module is damaged.
Possible causes
Source: SINAMICS S210_SIMOTICS S-1FK2 and S-1FT2 P892