Siemens F07553 fault code meaning
Siemens / F07553
Series: G120-CU250S-2
Drive encoder: Encoder module configuration not supported
converter
Meaning: The encoder module does not support the requested configuration. If an error occurs in p0430 (cc = 0): - At least 1 bits are set in p0430 (requested functions) that are not set in r0458 (supported functions), except for bits 19, 28, 29, 30, and 31. - p1982 > 0 (pole position detection requested), but r0458.16 = 0 (pole position detection not supported). If an error occurs in p0437 (cc = 1): - At least 1 bits are set in p0437 (requested functions) that are not set in r0459 (supported functions).
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1051
Series: G120D, G220
Drive encoder: Encoder module configuration not supported
converter
Meaning:
Possible causes
Source: SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P884; SINAMICS G220 Converter P1353
Series: G130-G150
Drive encoder: Sensor Module configuration not sup
converter
Meaning:
Possible causes
Source: G150 P876
Series: S110
Drive encoder: Encoder module configuration not supported
servo drive
Meaning: The encoder module does not support the requested configuration. When an error occurs in p0430 (cc = 0): - At least 1 bits are set in p0430 (requested functions) that are not set in r0458 (supported functions), except for bits 19, 28, 29, 30, 31. - p1982 > 0 (pole position detection requested), but r0458.16 = 0 (pole position detection not supported).
Possible causes
Source: SINAMICS S110 P1036