Siemens F07460 fault code meaning
Siemens / F07460
Series: G120-CU250S-2, G120D, G130-G150, S120-S150
EPOS: End of reference point cam not found
converter
Meaning: During homing, the axis reached the end of the travel range when it reached the zero pulse, without detecting an edge on BI: p2612 "Reference cam". Maximum travel range: 2147483648 [LU] ... -2147483647 [LU]
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P976; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P876; SINAMICS G130_G150 P1621; SINAMICS S120_S150 P2766
Series: G210, G220
EPOS: Reference cam end point not found
converter
Meaning: In "active homing" mode, the axis reaches the end of the travel range when reaching the zero pulse, without detecting an edge at the "reference cam" binector input (c2612). Maximum travel range: 2147483648 [LU] ... - 2147483647 [LU]
Possible causes
Source: SINAMICS G210 converter P1120; SINAMICS G220 converter P1338
Series: S110
EPOS: End of reference point cam not found
servo drive
Meaning: During homing, the axis reached the end of the travel range when it reached the zero pulse, without detecting an edge on BI: p2612 "Reference cam". Maximum travel range: 2147483648 [LU] ... -2147483647 [LU]
Possible causes
Source: SINAMICS S110 P1022
Series: S200
EPOS: Reference cam end point not found
servo drive
Meaning: In "Active homing" mode, the axis reached the end of the traversing range when reaching the zero pulse, without detecting an edge on the "Reference cam" binary signal (c2612). Maximum traversing range: 2147483648 [LU] ... - 2147483647 [LU] System messages 12.3 Faults and alarms SINAMICS S200 Compact Servo Drive System with SIMOTICS S-1FL2 or S-1FL1 496 Operating Instructions, 10/2025, FW V6.5 HF1, A5E54029715B AB
Possible causes
Source: SINAMICS S200 Compact_SIMOTICS S-1FL2 and S-1FL1 P498
Series: S210
EPOS: Reference cam end point not found
servo drive
Meaning: In "Active homing" mode, the axis reached the end of the travel range while approaching the zero marker without detecting an edge on the binary signal "Reference cam" (c2612). Maximum travel range: 2147483648 [LU] ... - 2147483647 [LU] Faults and alarms 18.2 List of faults and alarms SINAMICS S210 servo drive system equipped with SIMOTICS S-1FK2 and S-1FT2 Operating Instructions, 05/2025, FW V6.4, A5E52380168F AF 1323
Possible causes
Source: SINAMICS S210_SIMOTICS S-1FK2 and S-1FT2 P1325
Series: S220
EPOS: Reference cam end point not found
converter
Meaning:
Possible causes
Source: SINAMICS S220 Converter P2304