Siemens F07452 fault code meaning

Siemens / F07452

Series: G120-CU250S-2

Position loop: Following error too large

converter

Meaning: The difference between the position reference and the actual position (dynamic following error mode, r2563) is greater than the tolerance (p2546). - The torque or acceleration capability of the drive has been exceeded. - The position measuring system has an error. - The position control direction is incorrect. - The mechanical system is jammed. - The run speed is too high or the change in the position reference is too large.

Possible causes

Source: SINAMICS G120, Control Unit CU250S-2 P975

Series: G120D, S120-S150

Position loop: Following error too large

converter

Meaning: The difference between the position setpoint and the actual position (dynamic following error mode, r2563) exceeds the tolerance (p2546). - The torque or acceleration capability of the drive has been exceeded. - There is an error in the position measuring system. - The encoder cable is interrupted. - The position control direction is incorrect. - The mechanism is jammed. - The run speed is too high or the difference between position setpoints is too large.

Possible causes

Source: SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P874; SINAMICS S120_S150 P2764

Series: G130-G150

LR: Following error too high

converter

Meaning:

Possible causes

Source: G150 P865

Series: G210, S220

Position loop: Following error too large

converter

Meaning: The difference between the position setpoint and the actual position (dynamic following error mode, r2563) exceeds the tolerance (p2546). - The torque or acceleration capability of the drive is exceeded. - Error in the position measuring system. - Encoder cable interruption. - Incorrect position control direction. - Mechanical system jammed. - Run speed too high or position setpoint difference too large.

Possible causes

Source: SINAMICS G210 converter P1118; SINAMICS S220 converter P2302

Series: G220

Position loop: Following error too large

converter

Meaning:

Possible causes

Source: SINAMICS G220 Converter P1335

Series: S110

Position loop: Following error too large

servo drive

Meaning: The difference between the position reference and the actual position (dynamic following error mode, r2563) is greater than the tolerance (p2546). - The torque or acceleration capability of the drive has been exceeded. - The position measuring system has an error. - The position control direction is incorrect. - The mechanical system is jammed. - The run speed is too high or the change in the position reference is too large.

Possible causes

Source: SINAMICS S110 P1020

Series: S200

Position loop: Following error too large

servo drive

Meaning: The difference between the position setpoint and the actual position (dynamic following error mode, r2563) exceeds the tolerance (p2546). - The torque or acceleration capability of the drive is exceeded. - Error in the position measuring system. - Encoder cable interruption. - Incorrect position control direction. - Mechanical system jammed. - Run speed too high or position setpoint difference too large.

Possible causes

Source: SINAMICS S200 PROFINET_SIMOTICS S-1FL2 P523

Series: S210

Position loop: Following error too large

servo drive

Meaning: The difference between the position setpoint and the actual position (dynamic following error mode, r2563) exceeds the tolerance (p2546). - The torque or acceleration capability of the drive is exceeded. - Error in the position measuring system. - Encoder cable interruption. - Incorrect position control direction. - Mechanical system jammed. - Run speed too high or position setpoint difference too large.

Possible causes

Source: SINAMICS S210_SIMOTICS S-1FK2 and S-1FT2 P1323