Siemens F07411 fault code meaning
Siemens / F07411
Series: G110M, G115D, G120D
Drive: Flux setpoint not reached during field excitation
converter
Meaning: The specified flux setpoint was not reached during the configured rapid field excitation (p1401.6 = 1), even though 90% of the maximum current was set. - Incorrect motor data. - The motor data does not match the motor connection (star/delta). - The motor current limit is set too low. - The induction motor (without an encoder, open-loop control) is limited by I2t. - The power unit is too small. - The field excitation time is too short.
Possible causes
Source: SINAMICS G110M P708; SINAMICS G115D P766; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P871
Series: G120-CU240B-E-2
Drive: Flux setpoint not reached during field excitation
converter
Meaning: Although 90% of the maximum current is set, the specified flux setpoint was not reached during the configured rapid field establishment (p1401.6 = 1). - Incorrect motor data. - A mismatch between the motor data and the motor connection (star/delta). - The motor current limit is set too low. - The induction motor (encoderless, open-loop control) is limited by I2t. - The power unit is too small. - The field establishment time is too short.
Possible causes
Source: SINAMICS G120, Control Unit CU240B-2_CU240E-2 P738
Series: G120-CU250S-2
Drive: Flux controller output limited
converter
Meaning: The specified flux setpoint was not reached during the configured rapid field excitation (p1401.6 = 1), even though 90% of the maximum current was set. - Incorrect motor data. - The motor data does not match the motor connection (star/delta). - The motor current limit is set too low. - The induction motor (without an encoder, open-loop control) is limited by I2t. - The power unit is too small. - The field excitation time is too short.
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1374
Series: G120X, G120XA
Drive: Flux setpoint not reached during field excitation
converter
Meaning: The specified flux reference was not reached during the configured rapid field buildup (p1401.6 = 1), although 90% of the maximum current was set. - Incorrect motor data. - The motor data does not match the motor connection (star/delta). - The motor current limit is set too low. - The induction motor (without an encoder, open-loop control) is limited by I2t. - The power unit is too small. - The field buildup time is too short.
Possible causes
Source: SINAMICS G120X Converter P1380; SINAMICS G120XA PN Converter P1291
Series: G130-G150
Drive: Flux setpoint not reached during field excitation
converter
Meaning: Although 90% is set to the maximum current, the specified flux setpoint was not reached during the configured rapid field buildup (p1401.6 = 1). - Incorrect motor data. - The motor data does not match the motor connection (star/delta). - The motor current limit setting is too low. - The induction motor (encoderless, open-loop control) is limited by I2t. - The motor module is too small. - The field buildup time p0346 is too small.
Possible causes
Source: SINAMICS G130_G150 P1611
Series: G200
Drive: Flux setting not reached during field excitation
converter
Meaning: Although 90% of the maximum current was set, the specified flux setting was not reached during the configured rapid field buildup (p1401.6 = 1). - Incorrect motor data. - The motor data does not match the motor connection (star/delta). - The motor current limit setting is too low. - The induction motor (without an encoder, open-loop control) is limited by I2t. - The power unit is too small. - The field buildup time is too short.
Possible causes
Source: SINAMICS G200 Basic converter P589
Series: S120-S150
Drive: Flux controller output limited
converter
Meaning: The specified flux setpoint cannot be reached despite the maximum field current (p1603) being set. - Incorrect motor data. - The motor data does not match the motor connection configuration (star/delta). - The motor current limits are set too low (p0640, p0323, p1603). - The induction motor (encoderless, open-loop control) is limited by I2t. - The motor module is too small.
Possible causes
Source: SINAMICS S120_S150 P2748
Series: S220
Drive: Flux controller output limited
converter
Meaning: The specified flux reference cannot be reached even with the maximum field current (p1603) set. - Incorrect motor data. - The motor data does not match the motor connection configuration (star/delta). - The motor current limits are set too low (p0640, p0323, p1603). - The induction motor (without an encoder, open-loop control) is limited by I2t. - The Motor Module is too small. - For an induction motor with a power unit overload reaction (p0290 = 2 or 10 or 12), the maximum current may be less than the field current.
Possible causes
Source: SINAMICS S220 converter P2284