Siemens F07410 fault code meaning

Siemens / F07410

Series: G110M, G115D, G120-CU250S-2, G120C, G120D, G130-G150, S120-S150

Drive: Current loop output limited

converter

Meaning: The condition "actual I_ = 0 and Uq_ setting _1 at the limit for longer than 16 ms" exists. Possible causes: - The motor is not connected or the motor contactor is open. - The motor data does not match the motor connection (star/delta). - No DC bus voltage is present. - The power unit is damaged. - The flying restart function is not enabled.

Possible causes

Source: SINAMICS G110M P708; SINAMICS G115D P766; SINAMICS G120, Control Unit CU250S-2 P1373; SINAMICS G120C P682; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P871; SINAMICS G130_G150 P1611; SINAMICS S120_S150 P2748

Series: G120-CU240B-E-2

Drive: Current loop output limited

converter

Meaning: The condition "I_ actual = 0 and Uq_ setting_1 exceeds 16 ms and is limited" exists. Possible causes: - The motor is not connected or the motor contactor is open. - There is a mismatch between the motor data and the motor connection (star/delta). - No DC bus voltage is present. - The power unit is damaged. - The "flying restart" function is not enabled.

Possible causes

Source: SINAMICS G120, Control Unit CU240B-2_CU240E-2 P737

Series: G120X

Drive: Current loop output limited

converter

Meaning: The condition "I_ actual = 0 and Uq_ setting_1 at the limit for longer than 16 ms" exists. Possible causes: - The motor is not connected or the motor contactor is open. - The motor data does not match the motor connection (star/delta). - No DC bus voltage is present. - The power unit is damaged. - The "flying restart" function is not enabled.

Possible causes

Source: SINAMICS G120X Converter P1380

Series: G120XA

Drive: Current loop output limited

converter

Meaning: The condition "I_ actual = 0 and Uq_ setting _1 at the limit for longer than 16 ms" is present. Possible causes: - The motor is not connected, or the motor contactor is open. - The motor data and motor connection (star/delta) mismatch. - No DC bus voltage is present. - The power unit is damaged. - The "flying restart" function is not activated. Alarms, faults and system messages 11.12 List of fault codes and alarm codes SINAMICS G120XA PN converter 1288 Operating Instructions, 09/2025, FW V1.05, A5E51610273B-AC

Possible causes

Source: SINAMICS G120XA PN converter P1290

Series: G200

Drive: Current controller output limited

converter

Meaning: The condition "actual I_ = 0 and setting Uq_ _1 at the limit for longer than 16 ms" exists. Possible causes: - The motor is not connected, or the motor contactor is open. - The motor data does not match the motor connection (star/delta). - No DC bus voltage. - The power unit is damaged. - Phase loss in the motor cable. - The "Flying restart" function is disabled.

Possible causes

Source: SINAMICS G200 Basic converter P588

Series: G210X

Drive: Current controller output limited

converter

Meaning:

Possible causes

Source: SINAMICS G210X Converter P970

Series: S110

Drive: Current loop output limited

servo drive

Meaning: The condition "I_ actual = 0 and Uq_ setting_1 at the limit for longer than 16 ms" is present. Possible causes: - The motor is not connected or the motor contactor is open. - No DC bus voltage is present. - The motor module is damaged.

Possible causes

Source: SINAMICS S110 P1011

Series: S200

Drive: Current controller output limited

servo drive

Meaning: The condition "I_ actual = 0 and Uq_ reference_1 at the limit for longer than 16 ms" is present. Possible causes: - The motor is not connected, or the motor contactor is open. - Phase loss in the motor cable. - No DC bus voltage. - The power unit is damaged.

Possible causes

Source: SINAMICS S200 PROFINET_SIMOTICS S-1FL2 P517

Series: S210

Drive: Current controller output limited

servo drive

Meaning: The condition "I_ actual = 0 and Uq_ setting _1 at the limit for longer than 16 ms" is present. Possible causes: - The motor is not connected or the motor contactor is open. - Phase loss in the motor cable. - No DC bus voltage. - The power unit is damaged.

Possible causes

Source: SINAMICS S210_SIMOTICS S-1FK2 and S-1FT2 P1319

Series: S220

Drive: Current controller output limited

converter

Meaning: The condition "actual I_ = 0 and reference Uq_ _1 at the limit for longer than 16 ms" is present. Possible causes: - The motor is not connected or the motor contactor is open. - The motor data does not match the motor connection configuration (star/delta). - No DC bus voltage is present. - The power unit is damaged. - Phase loss in the motor cable. - The flying restart function is not activated.

Possible causes

Source: SINAMICS S220 converter P2284