Siemens F07331 fault code meaning
Siemens / F07331
Series: G110M, G120C, G120D
Flying restart: Function not supported
converter
Meaning: Cannot connect to a rotating motor. The flying restart function is not supported under the following conditions: PMSM: Operation along the V/f characteristic curve using vector control without an encoder.
Possible causes
Source: SINAMICS G110M P706; SINAMICS G120C P680; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P870
Series: G115D
Flying restart: Function not supported
converter
Meaning: Cannot connect to a running motor.
Possible causes
Source: SINAMICS G115D P764
Series: G120-CU240B-E-2
Flying restart: Function not supported
converter
Meaning: Cannot connect to a running motor. The "flying restart" function is not supported under the following conditions: Permanent-magnet synchronous motor (PEM): operation with the V/f characteristic curve using encoderless vector control.
Possible causes
Source: SINAMICS G120, Control Unit CU240B-2_CU240E-2 P736
Series: G120-CU250S-2
Flying restart: Function not supported
converter
Meaning: The drive cannot be switched on while the motor is rotating. The "Flying restart" function is not supported under the following conditions: PMSM: Operation with the V/f characteristic curve using encoderless vector control. Note: PMSM: Permanent-magnet synchronous motor (permanent-magnet synchronous motor).
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1035
Series: G120X, G120XA
Flying restart: Function not supported
converter
Meaning: Cannot switch on to a rotating motor. The "flying restart" function is not supported under the following conditions: PMSM: Operation according to the V/f characteristic curve using vector control without an encoder.
Possible causes
Source: SINAMICS G120X Converter P1377; SINAMICS G120XA PN Converter P1288
Series: G130-G150
Flying restart: Function not supported
converter
Meaning: Cannot connect to a rotating motor. The "flying restart" function is not supported under the following conditions: Permanent-magnet synchronous motor (PMSM): - Operation with the V/f characteristic curve. - Encoderless operation without a connected voltage monitoring module (VSM). Separately excited synchronous motor (SESM): - Operation with the V/f characteristic curve.
Possible causes
Source: SINAMICS G130_G150 P1606