Siemens F07320 fault code meaning

Siemens / F07320

Series: G110M, G115D, G120D, G130-G150, S120-S150

Drive: Auto restart interruption

converter

Meaning: The preset number of restart attempts (p1211) has been exhausted because the fault could not be acknowledged within the monitoring time (p1213). Each new start attempt reduces the number of remaining starts (p1211). - The power unit monitoring time (p0857) has expired. - No auto restart occurs when exiting commissioning, completing motor identification, or optimizing the speed loop.

Possible causes

Source: SINAMICS G110M P705; SINAMICS G115D P763; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P869; SINAMICS G130_G150 P1605; SINAMICS S120_S150 P2738

Series: G120-CU230P-2, G120P-Cabinet

Auto restart interrupted

converter

Meaning:

Possible causes

Source: Converter SINAMICS G120, equipped with control unit CU230P-2 P492; SINAMICS G120P Cabinet P511

Series: G120-CU240B-E-2

Drive: Auto restart interruption

converter

Meaning: The preset number of restart attempts (p1211) has been exhausted because the fault could not be acknowledged within the monitoring time (p1213). Each new start attempt reduces the remaining number of start attempts (p1211). - No active switch-on command. - The power unit monitoring time (p0857) has expired. - No auto restart occurs when commissioning is exited, motor identification is completed, or the speed loop is optimized.

Possible causes

Source: SINAMICS G120, Control Unit CU240B-2_CU240E-2 P735

Series: G120-CU250S-2

Drive: Auto restart interruption

converter

Meaning: The preset number of restart attempts (p1211) has been exhausted because the fault could not be acknowledged within the monitoring time (p1213). Each new start attempt reduces the number of remaining start attempts (p1211). - No active switch-on command. - The monitoring time for the power unit (p0857) has expired. - No auto restart occurs when commissioning is exited, motor identification is completed, or the speed loop is optimized.

Possible causes

Source: SINAMICS G120, Control Unit CU250S-2 P1368

Series: G120C

Drive: Auto restart interruption

converter

Meaning: The preset number of restart attempts (p1211) has been exhausted because the fault could not be acknowledged within the monitoring time (p1213). Each new start attempt reduces the number of remaining start attempts (p1211). - The power unit monitoring time has expired. - No auto restart occurs when exiting commissioning, completing motor identification, or optimizing the speed loop.

Possible causes

Source: SINAMICS G120C P679

Series: G120X, G120XA

Drive: Auto restart interruption

converter

Meaning: The preset number of restart attempts (p1211) has been exhausted because the fault could not be acknowledged within the monitoring time (p1213). Each new start attempt reduces the number of remaining start attempts (p1211). - The power unit monitoring time (p0857) has expired. - Auto restart is not performed when exiting commissioning, after motor identification is completed, or during speed loop optimization.

Possible causes

Source: SINAMICS G120X Converter P1377; SINAMICS G120XA PN Converter P1287

Series: G200, G210, G220, S220

Drive: Auto restart interruption

converter

Meaning: The preset number of restart attempts (p1211) has been exhausted because the fault could not be acknowledged within the monitoring time (p1213). Each new start attempt reduces the number of remaining attempts (p1211). - The power unit monitoring time (p0857) elapsed. - Auto restart is not performed when exiting commissioning, after motor detection is completed, or during speed controller optimization.

Possible causes

Source: SINAMICS G200 converter P707; SINAMICS G210 converter P1103; SINAMICS G220 converter P1320; SINAMICS S220 converter P2271

Series: G210X

Drive: Auto restart interruption

converter

Meaning:

Possible causes

Source: SINAMICS G210X converter P965

Series: S110

Drive: Auto restart interruption

servo drive

Meaning: The preset number of restart attempts (p1211) has been exhausted because the fault could not be acknowledged within the monitoring time (p1213). Each new start attempt reduces the number of remaining start attempts (p1211). - No active switch-on command is present. - The power unit monitoring time (p0857) has elapsed. - Auto restart is not performed when exiting commissioning, after motor identification, or during speed loop optimization.

Possible causes

Source: SINAMICS S110 P1009