Siemens F07016 fault code meaning
Siemens / F07016
Series: G110M, G115D, G120D, G120XA
Drive: Motor temperature sensor fault message
converter
Meaning: A fault was detected when evaluating the temperature sensor configured in p0601. Possible causes: - Open circuit or sensor not connected (KTY: R > 2120 Ohm, PT1000: R > 2120 Ohm). - The measured resistance is too small (PTC: R < 20 Ohm, KTY: R < 50 Ohm, PT1000: R < 603 Ohm).
Possible causes
Source: SINAMICS G110M P702; SINAMICS G115D P760; SINAMICS G120D Control unit CU240D- 2_CU250D- 2 P866; SINAMICS G120XA PN converter P1283
Series: G120-CU230P-2
Motor temperature sensor fault
converter
Meaning:
Possible causes
Source: Converter SINAMICS G120, equipped with control unit CU230P-2 P492
Series: G120-CU240B-E-2
Drive: Motor temperature sensor fault message
converter
Meaning: A fault was detected when evaluating the temperature sensor configured in p0601. Possible causes: - Open circuit or sensor not connected (KTY: R > 2120 ohms). - Measured resistance too small (PTC: R < 20 ohms, KTY: R < 50 ohms). Note: When warning A07015 occurs, the time set in p0607 starts counting down. If the fault persists after this time expires, F07016 is output only after warning A07015 has been present for at least 50 seconds. See: p0607 (Temperature sensor fault delay time)
Possible causes
Source: SINAMICS G120 Control Unit CU240B_E-2 P665
Series: G120-CU250S-2
Drive: Motor temperature sensor fault message
converter
Meaning: A fault was detected when evaluating the temperature sensor set in p0601. Possible causes: - Open circuit or sensor not connected (KTY: R > 2120 Ohm, PT1000: R > 2120 Ohm). - Measured resistance too small (PTC: R < 20 Ohm, KTY: R < 50 Ohm, PT1000: R < 603 Ohm).
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1031
Series: G120C
"Motor temperature
converter
Meaning:
Possible causes
Source: SINAMICS G120C P611
Series: G120P-Cabinet
Fault: Motor temperature sensor error
converter
Meaning:
Possible causes
Source: SINAMICS G120P Cabinet P510
Series: G120X
Drive: Motor temperature sensor fault message
converter
Meaning:
Possible causes
Source: SINAMICS G120X converter P1372
Series: G130-G150
Drive: Motor temperature sensor fault message
converter
Meaning: A fault was detected while evaluating the temperature sensors configured in p0600 and p0601. Possible causes: - Open circuit or sensor not connected (KTY: R > 1630 Ohm, PT1000: R > 1720 Ohm). - Measured resistance too small (PTC: R < 20 Ohm, KTY: R < 50 Ohm, PT1000: R < 603 Ohm).
Possible causes
Source: SINAMICS G130_G150 P1599
Series: G200, G210
Drive: Fault message from motor temperature sensor
converter
Meaning:
Possible causes
Source: SINAMICS G200 Basic converter P578; SINAMICS G210 converter P1097
Series: S110
Drive: Motor temperature sensor fault message
servo drive
Meaning: A fault was detected when evaluating the temperature sensors configured in p0600 and p0601. Possible causes: - An open circuit or a sensor is not connected (KTY: R > 1630 Ohm). - The measured resistance is too small (PTC: R < 20 ohms, KTY: R < 50 ohms).
Possible causes
Source: SINAMICS S110 P1005