Siemens F07011 fault code meaning
Siemens / F07011
Series: G110M, G130-G150
"Motor overtemperature"
converter
Meaning:
Possible causes
Source: SINAMICS G110M P635;G150 P738
Series: G115D, G120-CU240B-E-2, G120C, G120D
Drive: Motor overtemperature
converter
Meaning: KTY84/PT1000: The motor temperature exceeded the fault threshold (p0605), or the delay period (p0606) expired after the alarm threshold (p0604) was exceeded. The response set in p0610 is executed. The alarm is cleared when the action threshold for open-circuit monitoring is exceeded or no sensor is connected (R > 2120 Ohm). PTC or bimetal normally closed contact: The action threshold of 1650 ohms was exceeded, or the normally closed contact opened, and the delay time (p0606) expired. The response set in p0610 is executed. Possible causes: - Motor overload. - Motor ambient temperature too high. - Open circuit or sensor not connected.
Possible causes
Source: SINAMICS G115D P759; SINAMICS G120 Control Unit CU240B- 2_CU240E- 2 P836; SINAMICS G120C P674; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P865
Series: G120-CU230P-2, G120P-Cabinet
Motor overheat
converter
Meaning:
Possible causes
Source: Converter SINAMICS G120, equipped with Control Unit CU230P-2 P492; SINAMICS G120P Cabinet P510
Series: G120-CU250S-2
Drive: Motor overtemperature
converter
Meaning: KTY: The motor temperature has exceeded the fault threshold (p0605), or the delay period (p0606) has expired after the alarm threshold (p0604) was exceeded. The reaction set in p0610 is executed. The alarm is withdrawn if the response threshold for open-circuit monitoring is exceeded or no sensor is connected (R > 2120 Ohm). PTC or bimetallic normally closed contact: The response threshold of 1650 ohms has been exceeded, or the normally closed contact is open, and the delay time (p0606) has expired. The reaction set in p0610 is executed. Possible causes: - Motor overload. - Motor ambient temperature too high. - Open circuit or sensor not connected.
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1360
Series: G120X
Drive: Motor overtemperature
converter
Meaning: KTY84/PT1000/PT100: The motor temperature has exceeded the fault threshold (p0605), or the delay has elapsed after the alarm threshold (p0604) was exceeded. The response set in p0610 is executed. When using KTY84/ PT1000, the alarm is cleared if the open-circuit monitoring response threshold is exceeded or no sensor is connected (R > 2120 Ohm). PTC or bimetal normally closed contact: The response threshold of 1650 ohms has been exceeded or the normally closed contact is open, and the delay time has elapsed. The response set in p0610 is executed. Possible causes: - Motor overload. - Motor ambient temperature too high. - Open circuit or sensor not connected.
Possible causes
Source: SINAMICS G120X converter P1371
Series: G120XA, G210X
Drive: Motor overheat
converter
Meaning:
Possible causes
Source: SINAMICS G120XA PN converter Compact Operating Instructions P8; SINAMICS G210X converter P957
Series: G200
Drive: Motor overheat
converter
Meaning: Without a sensor: The model temperature exceeded the fault threshold, or the delay time elapsed after the alarm threshold was exceeded. This triggers the configured response. PTC: The action threshold (p0750) was exceeded and the delay time elapsed. This triggers the configured response. Additional motor overload: The motor load is too large. Possible causes: - Motor overload. - Motor ambient temperature too high.
Possible causes
Source: SINAMICS G200 Basic converter P576
Series: S110
Drive: Motor overtemperature
servo drive
Meaning: KTY: The motor temperature has exceeded the fault threshold (p0605), or the delay period (p0606) has elapsed after the alarm threshold (p0604) was exceeded. PTC, bimetallic normally closed contact: The action threshold of 1650 ohms has been exceeded (SME: p4600..p4603; TM120 p4610..p4613 = 10 or 30); or the delay period p0606 has elapsed after 1650 ohms was exceeded (SME: p4600..p4603; TM120: p4610..p4613 = 12 or 32).
Possible causes
Source: SINAMICS S110 P1004
Series: S120-S150
Drive: Motor overtemperature
converter
Meaning:
Possible causes
Source: SINAMICS S120_S150 P2723
Series: S200
Drive: Motor overheat
servo drive
Meaning:
Possible causes
Source: SINAMICS S200 PROFINET_SIMOTICS S-1FL2 P510
Series: S210
Drive: Motor overtemperature
servo drive
Meaning: The calculated motor temperature is too high. Possible causes: - Motor overload. - Motor ambient temperature too high. - Sensor open.
Possible causes
Source: SINAMICS S210_SIMOTICS S-1FK2 and S-1FT2 P885