Siemens F07011 fault code meaning

Siemens / F07011

Series: G110M, G130-G150

"Motor overtemperature"

converter

Meaning:

Possible causes

Source: SINAMICS G110M P635;G150 P738

Series: G115D, G120-CU240B-E-2, G120C, G120D

Drive: Motor overtemperature

converter

Meaning: KTY84/PT1000: The motor temperature exceeded the fault threshold (p0605), or the delay period (p0606) expired after the alarm threshold (p0604) was exceeded. The response set in p0610 is executed. The alarm is cleared when the action threshold for open-circuit monitoring is exceeded or no sensor is connected (R > 2120 Ohm). PTC or bimetal normally closed contact: The action threshold of 1650 ohms was exceeded, or the normally closed contact opened, and the delay time (p0606) expired. The response set in p0610 is executed. Possible causes: - Motor overload. - Motor ambient temperature too high. - Open circuit or sensor not connected.

Possible causes

Source: SINAMICS G115D P759; SINAMICS G120 Control Unit CU240B- 2_CU240E- 2 P836; SINAMICS G120C P674; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P865

Series: G120-CU230P-2, G120P-Cabinet

Motor overheat

converter

Meaning:

Possible causes

Source: Converter SINAMICS G120, equipped with Control Unit CU230P-2 P492; SINAMICS G120P Cabinet P510

Series: G120-CU250S-2

Drive: Motor overtemperature

converter

Meaning: KTY: The motor temperature has exceeded the fault threshold (p0605), or the delay period (p0606) has expired after the alarm threshold (p0604) was exceeded. The reaction set in p0610 is executed. The alarm is withdrawn if the response threshold for open-circuit monitoring is exceeded or no sensor is connected (R > 2120 Ohm). PTC or bimetallic normally closed contact: The response threshold of 1650 ohms has been exceeded, or the normally closed contact is open, and the delay time (p0606) has expired. The reaction set in p0610 is executed. Possible causes: - Motor overload. - Motor ambient temperature too high. - Open circuit or sensor not connected.

Possible causes

Source: SINAMICS G120, Control Unit CU250S-2 P1360

Series: G120X

Drive: Motor overtemperature

converter

Meaning: KTY84/PT1000/PT100: The motor temperature has exceeded the fault threshold (p0605), or the delay has elapsed after the alarm threshold (p0604) was exceeded. The response set in p0610 is executed. When using KTY84/ PT1000, the alarm is cleared if the open-circuit monitoring response threshold is exceeded or no sensor is connected (R > 2120 Ohm). PTC or bimetal normally closed contact: The response threshold of 1650 ohms has been exceeded or the normally closed contact is open, and the delay time has elapsed. The response set in p0610 is executed. Possible causes: - Motor overload. - Motor ambient temperature too high. - Open circuit or sensor not connected.

Possible causes

Source: SINAMICS G120X converter P1371

Series: G120XA, G210X

Drive: Motor overheat

converter

Meaning:

Possible causes

Source: SINAMICS G120XA PN converter Compact Operating Instructions P8; SINAMICS G210X converter P957

Series: G200

Drive: Motor overheat

converter

Meaning: Without a sensor: The model temperature exceeded the fault threshold, or the delay time elapsed after the alarm threshold was exceeded. This triggers the configured response. PTC: The action threshold (p0750) was exceeded and the delay time elapsed. This triggers the configured response. Additional motor overload: The motor load is too large. Possible causes: - Motor overload. - Motor ambient temperature too high.

Possible causes

Source: SINAMICS G200 Basic converter P576

Series: S110

Drive: Motor overtemperature

servo drive

Meaning: KTY: The motor temperature has exceeded the fault threshold (p0605), or the delay period (p0606) has elapsed after the alarm threshold (p0604) was exceeded. PTC, bimetallic normally closed contact: The action threshold of 1650 ohms has been exceeded (SME: p4600..p4603; TM120 p4610..p4613 = 10 or 30); or the delay period p0606 has elapsed after 1650 ohms was exceeded (SME: p4600..p4603; TM120: p4610..p4613 = 12 or 32).

Possible causes

Source: SINAMICS S110 P1004

Series: S120-S150

Drive: Motor overtemperature

converter

Meaning:

Possible causes

Source: SINAMICS S120_S150 P2723

Series: S200

Drive: Motor overheat

servo drive

Meaning:

Possible causes

Source: SINAMICS S200 PROFINET_SIMOTICS S-1FL2 P510

Series: S210

Drive: Motor overtemperature

servo drive

Meaning: The calculated motor temperature is too high. Possible causes: - Motor overload. - Motor ambient temperature too high. - Sensor open.

Possible causes

Source: SINAMICS S210_SIMOTICS S-1FK2 and S-1FT2 P885