Siemens F06909 fault code meaning
Siemens / F06909
Series: G130-G150
Braking module internal Uce fault
converter
Meaning: In the power unit, collector-emitter voltage (Uce) monitoring of the power semiconductor has responded at the braking resistor switching device. Possible causes: - Short circuit at the braking resistor terminals. - The power semiconductor in the braking resistor switching device is damaged.
Possible causes
Source: SINAMICS G130_G150 P1596
Series: S120-S150
Braking module internal Uce fault
converter
Meaning:
Possible causes
Source: SINAMICS S120_S150 P2722