Siemens F06310 fault code meaning
Siemens / F06310
Series: G110M, G120D
Incorrect input voltage (p0210) parameter setting
converter
Meaning: The DC bus voltage measured after precharging is complete is outside the tolerance range. Permissible range: 1.16 * p0210 < r0070 < 1.6 * p0210.
Possible causes
Source: SINAMICS G110M P700; SINAMICS G120D Control unit CU240D- 2_CU250D- 2 P864
Series: G115D
Incorrect input voltage (p0210) parameter setting
converter
Meaning: The DC bus voltage measured after precharging is outside the tolerance range. Permissible range: 1.16 * p0210 < r0070 < 1.8 * p0210
Possible causes
Source: SINAMICS G115D P758
Series: G120-CU230P-2
Load voltage (p0210) parameter setting incorrect
converter
Meaning:
Possible causes
Source: Converter SINAMICS G120, equipped with control unit CU230P-2 P491
Series: G120-CU240B-E-2
Incorrect input voltage (p0210) parameter setting
converter
Meaning: The DC bus voltage measured after precharging is outside the tolerance range: 1.16 * p0210 < r0070 < 1.6 * p0210. This fault can be acknowledged only when the drive is switched off. See: p0210 (Device input voltage)
Possible causes
Source: SINAMICS G120 Control Unit CU240B_E-2 P664
Series: G120-CU250S-2
Incorrect input voltage (p0210) parameter setting
converter
Meaning: The DC bus voltage measured after precharging is outside the tolerance range. Permissible range: 1.16 * p0210 < r0070 < 1.6 * p0210.
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P964
Series: G120C
Incorrect input voltage (p0210) parameter setting
converter
Meaning:
Possible causes
Source: SINAMICS G120C P673
Series: G120P-Cabinet
Load voltage (p0210) parameter setting error. Check the input voltage setting and modify it if necessary (p0210).
converter
Meaning:
Possible causes
Source: SINAMICS G120P Cabinet P510
Series: G120X, G120XA
Input voltage (p0210) parameter setting error
converter
Meaning:
Possible causes
Source: SINAMICS G120X Converter P1370; SINAMICS G120XA PN Converter P1281
Series: G130-G150, S120-S150
Infeed: Incorrect input voltage (p0210) parameter setting
converter
Meaning: After precharging is complete, the input voltage Ueff is calculated from the measured DC bus voltage. This voltage Ueff is outside the input voltage tolerance range. Tolerance range: 85 % * p0210 < Ueff < 110 % * p0210
Possible causes
Source: SINAMICS G130_G150 P1592; SINAMICS S120_S150 P2712
Series: G200, G210X, G220, S220
Input voltage (p0210) parameter setting error
converter
Meaning: The DC bus voltage measured after precharging was completed is outside the tolerance range. Permissible range: 1.16 * p0210 < r0070 < 1.6 * p0210. Note: This fault can only be acknowledged when the drive is disabled. The test is repeated after p0210 is changed. See also: p0210 (device input voltage)
Possible causes
Source: SINAMICS G200 converter P700; SINAMICS G210X converter P957; SINAMICS G220 converter P1307; SINAMICS S220 converter P2246
Series: G210
Input voltage (p0210) parameter setting error
converter
Meaning:
Possible causes
Source: SINAMICS G210 converter P1094
Series: S110
Incorrect input voltage (p0210) parameter setting
servo drive
Meaning: After precharging is complete, the DC bus voltage measured on the AC/AC device is outside the tolerance range. Tolerance range: 1.16 * p0210 < r0070 < 1.6 * p0210. This fault can only be acknowledged when the drive is disabled. See: p0210 (device input voltage).
Possible causes
Source: SINAMICS S110 P1004
Series: S200
Input voltage (p0210) parameter setting error
servo drive
Meaning: The DC bus voltage measured on the AC/AC device after precharging is complete is outside the tolerance range. Tolerance range: 1.16 * p0210 < r0070 < 1.6 * p0210 Note: This fault can only be acknowledged when the drive is disabled. See also: p0210 (device input voltage)
Possible causes
Source: SINAMICS S200 PROFINET_SIMOTICS S-1FL2 P510
Series: S210
Input voltage (p0210) parameter setting error
servo drive
Meaning: The DC bus voltage measured on the AC/AC device after precharging is complete is outside the tolerance range. Tolerance range: 1.16 * p0210 < r0070 < 1.6 * p0210 Note: This fault can only be acknowledged when the drive is disabled. See also: p0210 (device input voltage)
Possible causes
Source: SINAMICS S210_SIMOTICS S-1FK2 and S-1FT2 P1314