Siemens F06310 fault code meaning

Siemens / F06310

Series: G110M, G120D

Incorrect input voltage (p0210) parameter setting

converter

Meaning: The DC bus voltage measured after precharging is complete is outside the tolerance range. Permissible range: 1.16 * p0210 < r0070 < 1.6 * p0210.

Possible causes

Source: SINAMICS G110M P700; SINAMICS G120D Control unit CU240D- 2_CU250D- 2 P864

Series: G115D

Incorrect input voltage (p0210) parameter setting

converter

Meaning: The DC bus voltage measured after precharging is outside the tolerance range. Permissible range: 1.16 * p0210 < r0070 < 1.8 * p0210

Possible causes

Source: SINAMICS G115D P758

Series: G120-CU230P-2

Load voltage (p0210) parameter setting incorrect

converter

Meaning:

Possible causes

Source: Converter SINAMICS G120, equipped with control unit CU230P-2 P491

Series: G120-CU240B-E-2

Incorrect input voltage (p0210) parameter setting

converter

Meaning: The DC bus voltage measured after precharging is outside the tolerance range: 1.16 * p0210 < r0070 < 1.6 * p0210. This fault can be acknowledged only when the drive is switched off. See: p0210 (Device input voltage)

Possible causes

Source: SINAMICS G120 Control Unit CU240B_E-2 P664

Series: G120-CU250S-2

Incorrect input voltage (p0210) parameter setting

converter

Meaning: The DC bus voltage measured after precharging is outside the tolerance range. Permissible range: 1.16 * p0210 < r0070 < 1.6 * p0210.

Possible causes

Source: SINAMICS G120, Control Unit CU250S-2 P964

Series: G120C

Incorrect input voltage (p0210) parameter setting

converter

Meaning:

Possible causes

Source: SINAMICS G120C P673

Series: G120P-Cabinet

Load voltage (p0210) parameter setting error. Check the input voltage setting and modify it if necessary (p0210).

converter

Meaning:

Possible causes

Source: SINAMICS G120P Cabinet P510

Series: G120X, G120XA

Input voltage (p0210) parameter setting error

converter

Meaning:

Possible causes

Source: SINAMICS G120X Converter P1370; SINAMICS G120XA PN Converter P1281

Series: G130-G150, S120-S150

Infeed: Incorrect input voltage (p0210) parameter setting

converter

Meaning: After precharging is complete, the input voltage Ueff is calculated from the measured DC bus voltage. This voltage Ueff is outside the input voltage tolerance range. Tolerance range: 85 % * p0210 < Ueff < 110 % * p0210

Possible causes

Source: SINAMICS G130_G150 P1592; SINAMICS S120_S150 P2712

Series: G200, G210X, G220, S220

Input voltage (p0210) parameter setting error

converter

Meaning: The DC bus voltage measured after precharging was completed is outside the tolerance range. Permissible range: 1.16 * p0210 < r0070 < 1.6 * p0210. Note: This fault can only be acknowledged when the drive is disabled. The test is repeated after p0210 is changed. See also: p0210 (device input voltage)

Possible causes

Source: SINAMICS G200 converter P700; SINAMICS G210X converter P957; SINAMICS G220 converter P1307; SINAMICS S220 converter P2246

Series: G210

Input voltage (p0210) parameter setting error

converter

Meaning:

Possible causes

Source: SINAMICS G210 converter P1094

Series: S110

Incorrect input voltage (p0210) parameter setting

servo drive

Meaning: After precharging is complete, the DC bus voltage measured on the AC/AC device is outside the tolerance range. Tolerance range: 1.16 * p0210 < r0070 < 1.6 * p0210. This fault can only be acknowledged when the drive is disabled. See: p0210 (device input voltage).

Possible causes

Source: SINAMICS S110 P1004

Series: S200

Input voltage (p0210) parameter setting error

servo drive

Meaning: The DC bus voltage measured on the AC/AC device after precharging is complete is outside the tolerance range. Tolerance range: 1.16 * p0210 < r0070 < 1.6 * p0210 Note: This fault can only be acknowledged when the drive is disabled. See also: p0210 (device input voltage)

Possible causes

Source: SINAMICS S200 PROFINET_SIMOTICS S-1FL2 P510

Series: S210

Input voltage (p0210) parameter setting error

servo drive

Meaning: The DC bus voltage measured on the AC/AC device after precharging is complete is outside the tolerance range. Tolerance range: 1.16 * p0210 < r0070 < 1.6 * p0210 Note: This fault can only be acknowledged when the drive is disabled. See also: p0210 (device input voltage)

Possible causes

Source: SINAMICS S210_SIMOTICS S-1FK2 and S-1FT2 P1314