Siemens F06300 fault code meaning
Siemens / F06300
Series: G220
"Infeed: Line voltage too high at power on"
converter
Meaning:
Possible causes
Source: SINAMICS G220 Converter P1145
Series: S120-S150
Infeed: Input voltage too high at switch-on
converter
Meaning: At power-on, the RMS input voltage Ueff is too high to ensure controlled operation without exceeding the maximum DC bus voltage p0280. Fault condition: Ueff * 1.5 > p0280.
Possible causes
Source: SINAMICS S120_S150 P2711
Series: S220
Infeed: Mains voltage too high at switch-on
converter
Meaning: At power-on, the RMS mains voltage Ueff is too high to ensure controlled operation without exceeding the maximum DC bus voltage p0280. Fault condition: Ueff * 1.5 > p0280.
Possible causes
Source: SINAMICS S220 converter P2244