Siemens F047 fault code meaning

Siemens / F047

Series: 6RA70

Configurable analog input

DC drive

Meaning: 1 fault (terminals 6 and 7) (valid in operating states ≤ o6). The fault message is activated when P710=2 (current input 4 to 20mA) and the input current is less than 2mA. Possible fault causes: Power supply cable open circuit; P710 set incorrectly.

Possible causes

Source: 6ra70_c P427