Siemens F046 fault code meaning
Siemens / F046
Series: 6RA70
Main reference
DC drive
Meaning: Configurable analog input fault (terminals 4 and 5) (valid in operating states ≤ o6). The fault message is activated when P700=2 (current input 4 to 20 mA) and the input current is less than 2mA. Possible fault causes: Power supply cable open circuit; P700 set incorrectly.
Possible causes
Source: 6ra70_c P427