Siemens F01513 fault code meaning

Siemens / F01513

Series: DCM-6RA80

BICO: Connections between different drive objects have different scaling

DC drive

Meaning: The required BICO connection has been established, and conversion using reference values is required between the BICO output and the BICO input. Different drive objects are interconnected, and the BICO output and BICO input have different scaling units, or the same scaling units but different reference values. Example 1: The scaling unit of the BICO output is "voltage", and the scaling unit of the BICO input is "current". The BICO input and BICO output are in different drive objects. Conversion between the BICO output and the BICO input uses factor p2002/p2001. p2002: Contains the reference value for "current". p2001: Contains the reference value for "voltage". Example 2: The scaling unit of the BICO output is "voltage", in drive object 1 (DO1); the scaling unit of the BICO input is "voltage", in drive object 2 (DO2). The values of the "voltage" reference parameter p2001 differ between these two drive objects. Between the BICO output and the BICO input, the factor used is p2001(DO1)/p200

Possible causes

Source: SINAMICS DCM, Parameter Manual, firmware version 1.5 SP2 (based on 5.1 SP2) P977

Series: G110M, G120-CU240B-E-2, G120-CU250S-2, G120C, G120D

BICO: Connections between different drive objects have different scaling

converter

Meaning: The required BICO connection has been established, and the BICO output and BICO input require conversion using reference values. Different drive objects are interconnected, and the BICO output and BICO input have different scaling units; or they have the same scaling units but different reference values. Example 1: The scaling unit of the BICO output is "voltage", and the scaling unit of the BICO input is "current". The BICO input and BICO output belong to different drive objects. Conversion between the BICO output and BICO input uses factor p2002/p2001. p2002: Reference value for "current". p2001: Reference value for "voltage". Example 2: The scaling unit of the BICO output is "voltage", in drive object 1(DO1); the scaling unit of the BICO input is "voltage", in drive object 2(DO2). The values of the "voltage" reference parameter p2001 differ between these two drive objects. Conversion between the BICO output and BICO input uses factor p2001(

Possible causes

Source: SINAMICS G110M P677; SINAMICS G120 Control Unit CU240B- 2_CU240E- 2 P803; SINAMICS G120, Control Unit CU250S-2 P1313; SINAMICS G120C P652; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P829

Series: G115D, G130-G150

BICO: Connections between different drive objects have different scaling

converter

Meaning:

Possible causes

Source: SINAMICS G115D P724; SINAMICS G130_G150 P1482

Series: G120X, G120XA

BICO: Connections between different drive objects have different scaling

converter

Meaning: The required BICO connection has been established, and the BICO output and BICO input require conversion using reference values. Different drive objects are interconnected, and the BICO output and BICO input have different scaling units, or the same scaling units but different reference values. Example 1: The scaling unit of the BICO output is "voltage", and the scaling unit of the BICO input is "current". The BICO input and BICO output are in different drive objects. Conversion between the BICO output and BICO input uses the factor p2002/p2001. p2002: Reference value for "current". p2001: Reference value for "voltage". Example 2: The scaling unit of the BICO output is "voltage", in drive object 1(DO1); the scaling unit of the BICO input is "voltage", in drive object 2(DO2). The values of the "voltage" reference parameter p2001 differ between these two drive objects. Conversion between the BICO output and BICO input uses the factor p2001(DO1)/p2001(

Possible causes

Source: SINAMICS G120X Converter P1360; SINAMICS G120XA PN Converter P1275

Series: S110

BICO: Connections between different drive objects have different scaling

servo drive

Meaning: The required BICO connection has been established, and the BICO output and BICO input require conversion using reference values. Different drive objects are interconnected, and the BICO output and BICO input have different scaling units; or they have the same scaling units but different reference values. Example 1: The scaling unit of the BICO output is "voltage", and the scaling unit of the BICO input is "current". The BICO input and BICO output belong to different drive objects. Conversion between the BICO output and BICO input uses factor p2002/p2001. p2002: Reference value for "current". p2001: Reference value for "voltage". Example 2: The scaling unit of the BICO output is "voltage", in drive object 1(DO1); the scaling unit of the BICO input is "voltage", in drive object 2(DO2). The values of the "voltage" reference parameter p2001 differ between these two drive objects. Conversion between the BICO output and BICO input uses factor p2001(

Possible causes

Source: SINAMICS S110 P950

Series: S120-S150

BICO: Connections between different drive objects have different scaling

converter

Meaning: The required BICO connection has been established, and the BICO output and BICO input require conversion using reference values. Different drive objects are interconnected, and the BICO output and BICO input have different scaling units, or the same scaling units but different reference values. Example 1: The scaling unit of the BICO output is "voltage", and the scaling unit of the BICO input is "current". The BICO input and BICO output are in different drive objects. Conversion between the BICO output and BICO input uses factor p2002/p2001. p2002: Reference value for "current" p2001: Reference value for "voltage" Example 2: The scaling unit of the BICO output is "voltage", in drive object 1 (DO1); the scaling unit of the BICO input is "voltage", in drive object 2 (DO2). The values of the "voltage" reference parameter p2001 differ between these two drive objects. Between the BICO output and BICO input, factor p200 is used

Possible causes

Source: SINAMICS S120_S150 P2560