Siemens F007 fault code meaning

Siemens / F007

Series: 6RA70

Overvoltage

DC drive

Meaning: (Valid in operating states ≤ o4) The voltage at terminals 1U1, 1V1 or 1W1 and 3U1, 3W1 remains above the response threshold for longer than the “Restart” time set in P086. Response threshold for the armature supply voltage: ) % ( . 100 352 P 1 001 078 P + ×. Response threshold for the field supply voltage: ) % ( . 100 352 P 1 002 078 P + ×. Possible fault causes: Power supply overvoltage; monitoring values set too sensitively or incorrectly (P352, P078). Note: This monitoring function is disabled at the factory and can be enabled via parameter P820. r047, indices 002 ~ 016: 1 overvoltage occurred. i002: Phase number issuing the valid fault message. 0...: Phase UV. 1...: Phase VW. 2...: Phase WU. 3...: Field phase. i003: Incorrect voltage value (normalized to 16384). 4: Overvoltage duration exceeds the value set in parameter P086 (if setting > 0) -

Possible causes