Series: G120-CU250S-2

HF Damper: Damping voltage too high

converter

Meaning: The damper voltage has exceeded the alarm threshold. - The motor harmonic amplitude is too high and has reached the resonance frequency of the output filter. - The current loop has excited strong resonance in the output filter. When the damper voltage is too high, F37002 is issued.

Possible causes

Source: SINAMICS G120, Control Unit CU250S-2 P1609