Siemens A32920 fault code meaning
Siemens / A32920
Series: G120-CU250S-2
Encoder 2: Temperature sensor fault
converter
Meaning: %1, Channel number: %2 Drive object: CU250S_S, CU250S_S_CAN, CU250S_S_DP, CU250S_S_PN Reaction: None. Acknowledgment: None. Cause: A fault occurred during temperature sensor measurement. Fault cause: 1 (= 01 hexadecimal): Open circuit or sensor not connected (KTY:R > 1630 ohms). 2 (= 02 hexadecimal): The measured resistance is too small (PTC: R < 20 ohms, KTY: R < 50 ohms). Other values: For internal Siemens fault diagnostics only. Note on the message value: Detailed information is encoded in the message value (r0949/r2124) as follows: 0000yyxx hex: yy = channel number, xx = fault cause.
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1572
Series: G130-G150
Encoder 2: Temperature sensor fault
converter
Meaning:
Possible causes
Source: G150 P966
Series: S110
Encoder 2: Temperature sensor fault
servo drive
Meaning: %1, Channel number: %2 Drive object: SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN Reaction: None. Acknowledgment: None. Cause: A fault occurred during temperature sensor measurement.
Possible causes
Source: SINAMICS S110 P1180