Siemens A31419 fault code meaning
Siemens / A31419
Series: G120-CU250S-2
Encoder 1: Signal A or B exceeded tolerance
converter
Meaning: The amplitude/phase/offset compensation for signal A or signal B has reached its limit. Amplitude error compensation: amplitude B/ amplitude A = 0.78 ... 1.27. Phase: <84 degrees or >96 degrees. SMC20: deviation compensation: +/-140mV. SMC10: deviation compensation: +/-650mV.
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1109
Series: G130-G150
Encoder 1: Track A or B outside the tolerance rang
converter
Meaning:
Possible causes
Source: G150 P937