Siemens A30057 fault code meaning

Siemens / A30057

Series: G110M, G115D, G120C, G120D, G130-G150, S120-S150

Power unit: Power supply imbalance

converter

Meaning: A frequency component in the DC bus voltage indicates power supply asymmetry or power supply phase loss, or possibly motor phase loss. Fault F30011 is output no later than 5 minutes after this alarm occurs. The exact time depends on the power unit type and the respective frequency. For Booksize and Chassis power units, the time also depends on how long the alarm has already been present.

Possible causes

Source: SINAMICS G110M P744; SINAMICS G115D P800; SINAMICS G120C P714; SINAMICS G120D control unit CU240D- 2_CU250D- 2 P922; SINAMICS G130_G150 P1733; SINAMICS S120_S150 P2901

Series: G120-CU240B-E-2, G120-CU250S-2

Power unit: Power supply imbalance

converter

Meaning: Supply imbalance or supply phase loss was detected from a frequency component of the DC bus voltage. Motor phase loss is also possible. Fault F30011 is output no later than 5 minutes after this alarm occurs. The exact time depends on the power unit type and the respective frequency. For Booksize and Chassis power units, the time also depends on how long the alarm has already been present.

Possible causes

Source: SINAMICS G120, Control Unit CU240B-2_CU240E-2 P770; SINAMICS G120, Control Unit CU250S-2 P1024

Series: G120X, G120XA

Power unit: Power supply imbalance

converter

Meaning: Power supply asymmetry, power supply phase loss, or possibly motor phase loss was detected from a frequency component of the DC bus voltage. Fault F30011 is issued no later than 5 minutes after this alarm occurs. The actual time depends on the power unit type and the respective frequency. For Booksize and Chassis power units, the time also depends on how long the alarm has already been present.

Possible causes

Source: SINAMICS G120X converter P1414; SINAMICS G120XA PN converter P1323

Series: G200, G210, G210X, G220, S220

Power unit: Mains imbalance

converter

Meaning: Abnormal frequencies have been detected in the DC bus voltage, indicating possible mains imbalance or phase loss. A motor phase may also be missing. If these frequencies persist with the same or greater amplitude, fault F30011 is issued after a device-specific time.

Possible causes

Source: SINAMICS G200 converter P762; SINAMICS G210 converter P1202; SINAMICS G210X converter P1028; SINAMICS G220 converter P1460; SINAMICS S220 converter P2474

Series: S200

Power unit: Power supply imbalance

servo drive

Meaning: A frequency component in the DC bus voltage indicates power supply asymmetry, mains phase loss, or possibly motor phase loss. If these frequency components persist with the same or greater amplitude, fault F30011 is output after a device-specific time. The alarm value is intended only for internal Siemens fault diagnostics.

Possible causes

Source: SINAMICS S200 Compact_SIMOTICS S-1FL2 and S-1FL1 P532

Series: S210

Power unit: Power supply imbalance

servo drive

Meaning: A frequency component in the DC bus voltage indicates power supply asymmetry, power supply phase loss, or possibly motor phase loss. If these frequency components persist with the same or greater amplitude, fault F30011 is output after a device-specific time. The alarm value is intended only for internal Siemens fault diagnostics.

Possible causes

Source: SINAMICS S210_SIMOTICS S-1FK2 and S-1FT2 P1361