Siemens A30032 fault code meaning

Siemens / A30032

Series: G110M, G120-CU250S-2, G120C, G120D

Power unit: Hardware current limit activated for phase V

converter

Meaning: Hardware current limiting has responded in phase V. Pulses in this phase are inhibited for one pulse period. - Incorrect closed-loop control parameter settings. - Fault in the motor or power cable. - The power cable exceeds the maximum permissible length. - The motor load is too large. - The power unit is damaged.

Possible causes

Source: SINAMICS G110M P741; SINAMICS G120, control unit CU250S-2 P1463; SINAMICS G120C P711; SINAMICS G120D control unit CU240D- 2_CU250D- 2 P920

Series: G115D, G120X, G120XA

Power unit: Hardware current limit activated for phase V

converter

Meaning:

Possible causes

Source: SINAMICS G115D P796; SINAMICS G120X converter P1410; SINAMICS G120XA PN converter P1320

Series: G120-CU240B-E-2

Power unit: Hardware current limit activated for phase V

converter

Meaning: Hardware current limiting has responded in phase V. Pulses in this phase are inhibited for one pulse period. - Incorrect closed-loop control parameter settings. - Fault in the motor or power cable. - The power cable exceeds the maximum permissible length. - The motor load is too large. - The power unit is damaged. Note: If hardware current limiting responds in phase U, V or W of the power module, warning A30031 is always output.

Possible causes

Source: SINAMICS G120 Control Unit CU240B_E-2 P689

Series: G130-G150

Power unit: Hardware current limiting, phase V

converter

Meaning:

Possible causes

Source: G150 P912

Series: G200, G210, G210X, G220

Power unit: Hardware current limit for phase V

converter

Meaning: The hardware current limit for phase V has responded. Pulses in this phase are inhibited for one pulse period. - Incorrect closed-loop control parameter settings. - Fault in the motor or power cable. - The power cable exceeds the maximum permissible length. - The motor load is too large. - The power unit is damaged.

Possible causes

Source: SINAMICS G200 converter P756; SINAMICS G210 converter P1196; SINAMICS G210X converter P1022; SINAMICS G220 converter P1455

Series: S200

Power unit: Hardware current limit for phase V

servo drive

Meaning: The hardware current limit for phase V has been activated. Pulses in this phase are blocked for one pulse period. - Incorrect closed-loop control parameter settings. - Faulty motor or power supply cable. - Power supply cable exceeds the maximum permissible length. - Motor load too large. - Power unit damaged.

Possible causes

Source: SINAMICS S200 Compact_SIMOTICS S-1FL2 and S-1FL1 P528