Siemens A08757 fault code meaning

Siemens / A08757

Series: G110M, G120-CU240B-E-2, G120-CU250S-2, G120C, G130-G150, S120-S150

CAN: COB-ID setting invalid

converter

Meaning: During online operation, the corresponding COB-ID must be set to invalid before mapping. Example: Change the mapping for RPDO 1 (p8710[0]). --> p8700[0] = C00006E0 Insert a 16-bit value (invalid COB-ID) --> Set p8710[0] as required --> p8700[0] valid COB-ID Log in

Possible causes

Source: SINAMICS G110M P731; SINAMICS G120, control unit CU240B-2_CU240E-2 P757; SINAMICS G120, control unit CU250S-2 P1445; SINAMICS G120C P701; SINAMICS G130_G150 P1705; SINAMICS S120_S150 P2870

Series: S110

CAN: COB-ID setting invalid

servo drive

Meaning: During online operation, the corresponding COB-ID must be set to invalid before mapping. Example: Change the mapping for RPDO 1 (p8710[0]). --> p8700[0] = C00006E0 Insert a 16-bit value (invalid COB-ID) --> Set p8710[0] as required --> p8700[0] valid COB-ID Log in

Possible causes

Source: SINAMICS S110 P1069