Siemens A07926 fault code meaning

Siemens / A07926

Series: G110M, G115D, G120-CU240B-E-2, G120-CU250S-2, G120D, G120X, G120XA, G130-G150

Drive: Invalid envelope parameters

converter

Meaning: Invalid parameter values have been entered for the load monitoring envelope. The following rule applies to the speed thresholds: p2182 < p2183 < p2184. The following rules apply to the torque thresholds: p2185 > p2186; p2187 > p2188; p2189 > p2190. The load monitoring configuration and response must match. The individual ranges for load torque monitoring must not be exceeded.

Possible causes

Source: SINAMICS G110M P718; SINAMICS G115D P776; SINAMICS G120 Control Unit CU240B- 2_CU240E- 2 P853; SINAMICS G120, Control Unit CU250S-2 P1047; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P898; SINAMICS G120X Converter P1391; SINAMICS G120XA PN Converter P1302; SINAMICS G130_G150 P1673

Series: G200, G210, G210X, S220

Drive: Invalid envelope parameters

converter

Meaning: Invalid parameter values have been entered for the load supervision envelope. The speed thresholds must satisfy the following rule: p2182 < p2183 < p2184. The torque thresholds must satisfy the following rules: p2185 > p2186; p2187 > p2188; p2189 > p2190. Load supervision and the response must be consistent. The individual regions of load torque supervision must not overlap.

Possible causes

Source: SINAMICS G200 converter P726; SINAMICS G210 converter P1160; SINAMICS G210X converter P989; SINAMICS S220 converter P2365

Series: G220

"Envelop characteristic, parameter not valid"

converter

Meaning:

Possible causes

Source: SINAMICS G220 Converter P1113

Series: S110

Drive: Invalid envelope parameters

servo drive

Meaning: Invalid parameter values have been entered for the load supervision envelope. The speed thresholds must satisfy the following rule: p2182 < p2183 < p2184. The torque thresholds must satisfy the following rules: p2185 > p2186 p2187 > p2188 p2189 > p2190.

Possible causes

Source: SINAMICS S110 P1055

Series: S120-S150

Drive: Invalid envelope parameters

converter

Meaning:

Possible causes

Source: SINAMICS S120_S150 P2825