Siemens A07903 fault code meaning

Siemens / A07903

Series: G110M, G120-CU240B-E-2

Drive: Motor speed difference

converter

Meaning: The speed difference between the setpoint (p2151) and the actual speed (r2169) has exceeded the tolerance threshold (p2163) for longer than the delay time (p2164, p2166). This alarm is output only when p2149.0 = 1. Possible causes: The load torque is greater than the torque setpoint. - The torque/current/power limit is reached during acceleration. If the limits are insufficient, the selected drive may be too small. - In torque control, the speed setpoint does not track the actual speed. - When the Vdc controller is valid. In V/f control, the activated I_max controller detects an overload. See: p2149 (Monitoring configuration)

Possible causes

Source: SINAMICS G110M P716; SINAMICS G120, Control Unit CU240B-2_CU240E-2 P744

Series: G115D

Drive: Motor speed difference

converter

Meaning: The speed difference between the setpoint (p2151) and the actual speed (r2169) has exceeded the tolerance threshold (p2163) for longer than the delay time (p2164, p2166). This alarm is output only when p2149.0 = 1. Possible causes: - The load torque is greater than the torque setpoint. - The torque/current/power limit is reached during acceleration. If the limits are insufficient, the selected drive may be too small. - In torque control, the speed setpoint does not track the actual speed. - The Vdc controller is active. In V/f control, activation of the I_max controller indicates an overload. See also: p2149 (Monitoring configuration).

Possible causes

Source: SINAMICS G115D P774

Series: G120-CU230P-2, G120C, G120D, G120P-Cabinet

Motor speed difference

converter

Meaning:

Possible causes

Source: Converter SINAMICS G120, with Control Unit CU230P-2 P495; Converter SINAMICS G120C P406; Converter SINAMICS G120D, with Control Unit CU250D-2 P330; SINAMICS G120P Cabinet P512

Series: G120-CU250S-2

Drive: Motor speed difference

converter

Meaning: The speed difference between the two setpoints (p2151, p2154) and the actual speed (r2169) has exceeded the tolerance threshold (p2163) for longer than the delay time (p2164, p2166). This alarm is output only when p2149.0 = 1. Possible causes: - The load torque is greater than the torque setpoint. - The torque/current/power limit is reached during acceleration. If the limits are insufficient, the selected drive may be too small. - In torque control, the speed setpoint does not track the actual speed. - When the Vdc controller is valid. In V/f control, the Imax controller detects an overload. See: p2149 (Monitoring configuration).

Possible causes

Source: SINAMICS G120, Control Unit CU250S-2 P1416

Series: G120X, G120XA

Drive: Motor speed difference

converter

Meaning: The speed difference between the setpoint (p2151) and the actual speed (r2169) has exceeded the tolerance threshold (p2163) for longer than the delay time (p2164, p2166). This alarm is output only when p2149.0 = 1. Possible causes: - The load torque is greater than the torque setpoint. - The torque/current/power limit is reached during acceleration. If the limit is insufficient, the selected drive may be too small. - The Vdc controller is active. In V/f control, activation of the I_max controller indicates an overload. See also: p2149 (monitoring configuration)

Possible causes

Source: SINAMICS G120X converter P1389; SINAMICS G120XA PN converter P1300

Series: G130-G150

"Motor

converter

Meaning:

Possible causes

Source: G150 P734

Series: G210, S220

Drive: Motor speed difference

converter

Meaning: The absolute difference between the speed setpoint (c2151) and the actual speed (r2169) has exceeded the tolerance threshold (p2163) for longer than the delay time (p2164, p2166). This alarm is output only when p2149.0 = 1. Possible causes: - The load torque is greater than the torque setpoint. - The torque/current/power limit is reached during acceleration. If the limit is insufficient, the selected drive may be too small. - In torque control, the actual speed does not track the speed setpoint. - The Vdc controller is active. - Pulse injection is active and the torque limit (p1557) subsequently takes effect. In V/f control, the I_max controller detects an overload when activated. See also: p2149 (Monitoring configuration)

Possible causes

Source: SINAMICS G210 converter P1157; SINAMICS S220 converter P2357

Series: S110

Drive: Motor speed difference

servo drive

Meaning: The speed differences between the two setpoints (p2151, p2154) and the actual speed (r2169) exceed the tolerance threshold (p2163) and the permissible values (p2164, p2166). This alarm is output only when p2149.0 = 1. Possible causes: The load torque is greater than the torque setpoint. - The torque/current/power limits are reached during acceleration. If the limits are insufficient, the selected drive may be too small. - In torque control, the speed setpoint does not track the actual speed. - The Vdc controller is active. In V/f control, the Imax controller detects an overload. See: p2149 (Supervision configuration).

Possible causes

Source: SINAMICS S110 P1051