Siemens A07892 fault code meaning

Siemens / A07892

Series: G110M

Drive: Pump/fan no-load monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected operation without load. The pump is running without lubrication (no pumped liquid), or the fan drive belt is too smooth. The set detection torque threshold may be too low (p2191). See: p2181 (Load monitoring response), p2191 (No-load torque threshold), p2193 (Load monitoring configuration).

Possible causes

Source: SINAMICS G110M P714

Series: G115D, G120-CU240B-E-2

Drive: Pump/fan no-load monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected no-load operation. The pump is running without lubrication (no fluid being pumped), or the fan drive belt is too smooth. The configured detection torque threshold (p2191) may be too low. See also: p2181 (load monitoring response), p2191 (no-load torque threshold), p2193 (load monitoring configuration).

Possible causes

Source: SINAMICS G115D P772; SINAMICS G120 Control Unit CU240B- 2_CU240E- 2 P849

Series: G120-CU230P-2

Load monitoring: Pump/fan no load

converter

Meaning:

Possible causes

Source: Converter SINAMICS G120, equipped with control unit CU230P-2 P494

Series: G120-CU250S-2

Drive: Pump/fan no-load monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected no-load operation. The pump is running without lubrication (no pumped liquid), or the fan drive belt is too smooth. The detection torque threshold setting may be too low (p2191). See: p2181 (Load monitoring response), p2193 (Load monitoring configuration).

Possible causes

Source: SINAMICS G120, Control Unit CU250S-2 P1043

Series: G120C

Drive: Pump/fan no-load monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected no-load operation. The pump is running dry (no pumped liquid), or the fan drive belt is too smooth. The detection torque threshold setting may be too low (p2191). See also: p2191 (No-load torque threshold).

Possible causes

Source: SINAMICS G120C P686

Series: G120D

Drive: Pump/fan no-load monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected no-load operation. The pump is running dry (no pumped liquid), or the fan drive belt is too smooth. The detection torque threshold setting may be too low (p2191). See also: p2181 (Load monitoring response), p2193 (Load monitoring configuration).

Possible causes

Source: SINAMICS G120D control unit CU240D- 2_CU250D- 2 P894

Series: G120X

Drive: Pump/fan no-load monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected operation without a load. The pump is running dry (no fluid being pumped), or the fan drive belt is too smooth. The detection torque threshold setting may be too low (p2191). See also: p2181, p2191, p2193

Possible causes

Source: SINAMICS G120X converter P1387

Series: G120XA

Drive: Pump/fan no-load monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected no-load operation. The pump is running dry (no pumped fluid), or the fan drive belt is too smooth. The detection torque threshold may be set too low (p2191). See also: p2181, p2191, p2193 Alarms, faults and system messages 11.11 List of fault codes and alarm codes SINAMICS G120XA USS converter Operating Instructions, 09/2025, FW V1.04, A5E44751205F AH 1245

Possible causes

Source: SINAMICS G120XA USS converter P1247

Series: G210, G210X, G220, S220

Drive: Pump/fan no-load monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Pump/fan monitoring has detected no-load operation. The pump is running dry (no medium to convey), or the fan drive belt has broken. The configured detection torque threshold may be too low (p2191). See also: p2181 (Load monitoring response), p2191 (No-load torque threshold), p2193 (Load monitoring configuration).

Possible causes

Source: SINAMICS G210 converter P1153; SINAMICS G210X converter P982; SINAMICS G220 converter P1370; SINAMICS S220 converter P2350