Siemens A07891 fault code meaning

Siemens / A07891

Series: G110M

Drive: Pump/fan stall monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected a locked rotor in the pump/fan. The set locked rotor torque threshold (p2168) may be too low (e.g., during a heavy-load start). See: p2165 (Locked rotor monitoring upper limit), p2168 (Locked rotor monitoring torque threshold), p2181 (Load monitoring response), p2193 (Load monitoring configuration).

Possible causes

Source: SINAMICS G110M P713

Series: G115D, G120-CU240B-E-2

Drive: Pump/fan stall monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected a locked rotor in the pump/fan. The configured locked rotor torque threshold (p2168) may be too low (e.g., for a start under heavy load). See also: p2165 (locked rotor monitoring upper limit), p2168 (torque threshold for locked rotor monitoring), p2181 (load monitoring response), p2193 (load monitoring configuration).

Possible causes

Source: SINAMICS G115D P771; SINAMICS G120 Control Unit CU240B- 2_CU240E- 2 P849

Series: G120-CU230P-2

Load monitoring: Pump/fan stalled

converter

Meaning:

Possible causes

Source: Converter SINAMICS G120, equipped with control unit CU230P-2 P494

Series: G120-CU250S-2

Drive: Pump/fan stall monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected a locked rotor in the pump/fan. The locked rotor torque threshold setting (p2168) may be too low (e.g., for a start under heavy load). See: p2181 (Load monitoring response), p2193 (Load monitoring configuration).

Possible causes

Source: SINAMICS G120, Control Unit CU250S-2 P1042

Series: G120C

Drive: Pump/fan stall monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected a locked rotor in the pump/fan. The locked rotor torque threshold setting (p2168) may be too low (e.g., during a start under heavy load). See also: p2165 (Locked rotor monitoring upper limit), p2168 (Torque threshold for locked rotor monitoring).

Possible causes

Source: SINAMICS G120C P686

Series: G120D

Drive: Pump/fan stall monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected a locked rotor in the pump/fan. The configured locked rotor torque threshold (p2168) may be too low (e.g., during a start under heavy load). See also: p2181 (Load monitoring response), p2193 (Load monitoring configuration).

Possible causes

Source: SINAMICS G120D control unit CU240D- 2_CU250D- 2 P894

Series: G120X

Drive: Pump/fan stall monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected a locked rotor in the pump/fan. The locked rotor torque threshold setting (p2168) may be too low (e.g., during a start under heavy load). See also: p2165, p2168, p2181, p2193.

Possible causes

Source: SINAMICS G120X converter P1387

Series: G120XA

Drive: Pump/fan stall monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected a locked rotor in the pump/fan. The locked rotor torque threshold (p2168) may be set too low (e.g., for a start under heavy load). See also: p2165, p2168, p2181, p2193 Alarms, faults and system messages 11.12 List of fault codes and alarm codes SINAMICS G120XA PN converter Operating Instructions, 09/2025, FW V1.05, A5E51610273B-AC 1295

Possible causes

Source: SINAMICS G120XA PN converter P1297

Series: G210, S220

Drive: Pump/fan stall monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected a locked rotor in the pump/fan. The configured locked rotor torque threshold (p2168) may be too low (for example, during a start under heavy load). See also: p2165 (Locked rotor monitoring upper limit), p2168 (Torque threshold for locked rotor monitoring), p2181 (Load monitoring response), p2193 (Load monitoring configuration).

Possible causes

Source: SINAMICS G210 converter P1153; SINAMICS S220 converter P2350

Series: G210X

Drive: Pump/fan stall monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected a locked rotor in the pump/fan. The configured locked rotor torque threshold (p2168) may be too low (e.g., for a start under heavy load). See also: p2165 (Locked rotor monitoring upper limit), p2168 (Torque threshold for locked rotor monitoring), p2181 (Load monitoring response), p2193 (Load monitoring configuration). Faults and alarms 5.2 List of faults and alarms SINAMICS G210X Converter Parameter Manual, 07/2026, FW V6.7, A5E54375466F AA 979

Possible causes

Source: SINAMICS G210X Converter P981

Series: G220

Drive: Pump/fan stall monitoring

converter

Meaning: Load monitoring is configured for a pump or fan (p2193 = 4, 5). Monitoring has detected a locked rotor in the pump/fan. The locked rotor torque threshold setting (p2168) may be too low (for example, during a start under heavy load). See also: p2165, p2168, p2181, p2193

Possible causes

Source: SINAMICS G220 Converter P1369