Siemens A07487 fault code meaning
Siemens / A07487
Series: G120-CU250S-2, G120D, G130-G150, S120-S150
EPOS: Run task cancellation missing
converter
Meaning: In "Traversing blocks" or "Direct reference input/MDI" mode, the 1 signal is absent at the "No traversing task cancellation/traversing task cancellation" binector input (Bl:p2641) when operation is started.
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1390; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P880; SINAMICS G130_G150 P1628; SINAMICS S120_S150 P2772
Series: G210, G220, S220
EPOS: Run task cancellation missing
converter
Meaning: In the "Traversing blocks" or "Direct reference input/MDI" operating mode, the binary signal sink "No traversing task cancellation/Traversing task cancellation" (c2641) did not provide the 1 signal to start the run.
Possible causes
Source: SINAMICS G210 converter P1127; SINAMICS G220 converter P1344; SINAMICS S220 converter P2312
Series: S110
EPOS: Run task cancellation missing
servo drive
Meaning: In "Traversing blocks" or "Direct reference input/MDI" mode, the 1 signal is absent at the "No traversing task cancellation/traversing task cancellation" binector input (Bl:p2641) when operation is started.
Possible causes
Source: SINAMICS S110 P1027
Series: S200
EPOS: Run task cancellation missing
servo drive
Meaning: In the "Traversing blocks" or "Direct reference input/MDI" operating mode, the binary signal sink "No traversing task cancellation/Traversing task cancellation" (c2641) did not provide the 1 signal to start the run.
Possible causes
Source: SINAMICS S200 PROFINET_SIMOTICS S-1FL2 P532
Series: S210
EPOS: Run task cancellation missing
servo drive
Meaning: In the "Traversing block" or "Direct reference input/MDI" operating mode, the binary signal sink "No traversing task cancellation/Traversing task cancellation" (c2641) has not received the 1 signal required to start traversing.
Possible causes
Source: SINAMICS S210_SIMOTICS S-1FK2 and S-1FT2 P1332