Siemens A07091 fault code meaning
Siemens / A07091
Series: S120-S150
Drive: Measured current loop dynamic response invalid
converter
Meaning: When one-button tuning (p5300 = 1) is activated, the current loop is measured after pulses are enabled. This measurement indicates a mismatch in the current loop settings. Possible causes: - Incorrect current loop settings. - PRBS amplitude setting too high (p5296).
Possible causes
Source: SINAMICS S120_S150 P2732
Series: S200
Drive: Measured current controller dynamic response invalid
servo drive
Meaning: When one-button tuning (p5300 = 1) is activated, the current controller is measured after pulse enable. The measurement indicates a mismatch in the current controller settings. Possible causes: - Incorrect current controller settings. - PRBS amplitude set too high (p5296).
Possible causes
Source: SINAMICS S200 PROFINET_SIMOTICS S-1FL2 P514
Series: S210
Drive: Measured current controller dynamic response invalid
servo drive
Meaning: When one-button tuning (p5300 = 1) is activated, the current controller is measured after pulse enable. This measurement indicates a mismatch in the current controller settings. Possible causes: - Incorrect current controller settings. - The PRBS amplitude setting is too high (p5296).
Possible causes
Source: SINAMICS S210_SIMOTICS S-1FK2 and S-1FT2 P1316
Series: S220
Drive: Measured current controller dynamic response invalid
converter
Meaning: When one-button tuning (p5300 = 1) is activated, the current controller is measured after pulse enable. The measurement indicates a mismatch in the current controller settings. Possible causes: - Incorrect current controller settings. - PRBS amplitude set too high (p5296).
Possible causes
Source: SINAMICS S220 Converter P2264