Siemens A07015 fault code meaning
Siemens / A07015
Series: G110M, G115D, G120-CU240B-E-2, G120C, G120D, G120X, G120XA
Drive: Motor temperature sensor alarm message
converter
Meaning: A fault was detected when evaluating the temperature sensor configured in p0601, and the timer specified in p0607 started. If the fault persists after this time has elapsed, F07016 is output only after alarm A07015 has been active for at least 50 seconds. Possible causes: - Open circuit or sensor not connected (KTY: R > 2120 Ohm, PT1000: R > 2120 Ohm). - Measured resistance too small (PTC: R < 20 Ohm, KTY: R < 50 Ohm, PT1000: R < 603 Ohm).
Possible causes
Source: SINAMICS G110M P702; SINAMICS G115D P760; SINAMICS G120 Control Unit CU240B- 2_CU240E- 2 P837; SINAMICS G120C P675; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P866; SINAMICS G120X Converter P1372; SINAMICS G120XA PN Converter P1283
Series: G120-CU230P-2, G120P-Cabinet
Motor temperature sensor alarm
converter
Meaning:
Possible causes
Source: Converter SINAMICS G120, equipped with Control Unit CU230P-2 P492; SINAMICS G120P Cabinet P510
Series: G120-CU250S-2
Drive: Motor temperature sensor alarm message
converter
Meaning: A fault was detected while evaluating the temperature sensor configured in p0601, and the timer in p0607 starts. If the fault persists after this time expires, F07016 is output only after alarm A07015 has been active for at least 50 seconds. Possible causes: - Open circuit or sensor not connected (KTY: R > 2120 Ohm, PT1000: R > 2120 Ohm). - Measured resistance too small (PTC: R < 20 Ohm, KTY: R < 50 Ohm, PT1000: R < 603 Ohm).
Possible causes
Source: SINAMICS G120, Control Unit CU250S-2 P1031
Series: G130-G150
"Motor temperature
converter
Meaning:
Possible causes
Source: G150 P738
Series: G200
Drive: Motor temperature sensor alarm message
converter
Meaning: A fault was detected while evaluating the temperature sensors configured in p0600 and p0601. The timer in p0607 starts. If the fault persists after this time expires, output occurs only after alarm A07015 has been present for at least 50 seconds
Possible causes
Source: SINAMICS G200 Basic Converter P578
Series: G210
Drive: Motor temperature sensor alarm message
converter
Meaning: A fault was detected when evaluating the temperature sensors configured in p0600 and p0601. The timer in p0607 starts. If the fault persists after this time expires, F07016 is output, but no earlier than 50 milliseconds after alarm A07015 occurs. Possible causes: - Open circuit or sensor not connected (KTY: R > 1630 Ohm, Pt1000: R > 1720 Ohm, Pt100: R > 194 Ohm). - Measured resistance too small (PTC: R < 20 Ohm, KTY: R < 50 Ohm, Pt1000: R < 603 Ohm, Pt100: < 30 Ohm).
Possible causes
Source: SINAMICS G210 converter P1097
Series: G210X
Drive: Motor temperature sensor alarm message
converter
Meaning:
Possible causes
Source: SINAMICS G210X Converter P959
Series: S110
Drive: Motor temperature sensor alarm message
servo drive
Meaning: A fault was detected when evaluating the temperature sensors configured in p0600 and p0601, and the timer in p0607 starts. If the fault is still present when this time expires, F07016 is output only after alarm A07015 has been present for at least 50 seconds. Possible causes: - An open circuit or a sensor that is not connected (KTY:R > 1630 Ohm). - The measured resistance is too small (PTC: R < 20 ohms, KTY: R < 50 ohms).
Possible causes
Source: SINAMICS S110 P1005