Siemens A06215 fault code meaning
Siemens / A06215
Series: G220
Infeed: Total current too high
converter
Meaning: The filtered sum of the phase currents (i1 + i2 + i3) exceeds 3 % of the maximum power unit current (r13209). Possible causes: - A ground fault in the DC bus causes the total current (r13069[6]) to be too high. A DC component in the input current can damage or destroy the power unit, supply reactor, or supply filter! - Current measurement zero point compensation has not been performed (p3491, A06602). - The current measurement circuitry in the power unit is damaged.
Possible causes
Source: SINAMICS G220 converter P1306