Siemens A05002 fault code meaning
Siemens / A05002
Series: G110M, G115D, G120-CU240B-E-2, G120-CU250S-2, G120C, G120D
Power unit: Air inlet overheat
converter
Meaning: For chassis and cabinet power units: The air inlet temperature has exceeded the alarm threshold. The threshold for air-cooled power units is 42 °C (hysteresis 2K). The overheat response is set using p0290. If the air inlet temperature rises by a further 13K, fault F30035 is triggered.
Possible causes
Source: SINAMICS G110M P698; SINAMICS G115D P756; SINAMICS G120, Control Unit CU240B-2_CU240E-2 P729; SINAMICS G120, Control Unit CU250S-2 P1356; SINAMICS G120C P673; SINAMICS G120D Control Unit CU240D- 2_CU250D- 2 P863
Series: G120X, G120XA
Power unit: Air inlet overheat
converter
Meaning: For chassis and cabinet power units: The air inlet temperature has exceeded the alarm threshold. The threshold for air-cooled power units is 42 °C (hysteresis 2K). The overheat response is set using p0290. If the air inlet temperature rises by a further 13K, fault F30035 is triggered.
Possible causes
Source: SINAMICS G120X Converter P1369; SINAMICS G120XA PN Converter P1280
Series: G130-G150, S120-S150
Power unit: Air inlet overheat
converter
Meaning: The inlet air is overheated, and the alarm threshold has been exceeded. The threshold for air-cooled power units is 42 °C (hysteresis 2K). The overheat response is set via p0290. If the inlet air temperature rises by a further 13K, fault F30035 is triggered.
Possible causes
Source: SINAMICS G130_G150 P1583;SINAMICS S120_S150 P2695
Series: S110
Power unit: Air inlet overheat
servo drive
Meaning: The inlet air is overheated, and the alarm threshold has been exceeded. The threshold for air-cooled power units is 42 °C (hysteresis 2K). The overheat response is set via p0290. If the inlet air temperature rises by a further 13K, fault F30035 is triggered.
Possible causes
Source: SINAMICS S110 P1003
Series: S220
Power unit: Air inlet overheat
converter
Meaning: The inlet air has overheated, exceeding the alarm threshold. The threshold for air-cooled power units is 42 °C (hysteresis 2K). Set the overheat response using p0290. If the inlet air temperature rises further by 13K, fault F30035 is triggered.
Possible causes
Source: SINAMICS S220 converter P2217